Event

Event ID
91
Quality
Description

The event occurred while re-starting the ammonia production unit after a technical stop, a synthesis gas (50% hydrogen, 17% ammonia, methane and nitrogen) leak ignited on a flange located just after the synthesis reactor.
Emergency shutdown of the unit was executed and the fire was extinguished in a bit less than 1 hour.

The leaking at the flange was caused by a tightening torques of the bolt which were not adapted to the exceptional conditions prevailing during the accident. The short technical breakdown had induced a very quick temperature evolution with significant temperature gradients between the bolts and the flange.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
France
Date
Component involved
flange (bolts)
Failure mode
leak & ignition
Initiating cause
loss of tightness (thermal stress/cycling)
Root CAUSE analysis

The INITIATING CAUSE was loss of tightness of the flange due to the temperature gradient occurred during the technical shutdown. flange were not adapted to the situation.

The ROOT CAUSE (or at least an intermediate cause) is related to the fact that these temperature excursions had not been taken into account in the design of the reactor. Assuming that the operation of tightening had been executed by a contractor during the last inspection and maintenance works, another factor of the ROOT CAUSE could be the management of the contractor's operation by the site operator.

Root causes
Date entry in HIAD
28/02/2009

Facility

Application
Chemical industry
Sub-application
Ammonia production
Hydrogen supply chain stage
All components affected

flange

Process temperature range [C]
High temperature (100°C to 500°C)
Location type
Unknown
Location
industrial area
Operational condition
Pre-event occurrences

The ammonia producing unit had to be shut down rapidly due to a technical issue. At the moment of the re-start, the reactor had been shut down for 1h30.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Currency
Euro
Property loss (onsite)
360.000
Post-event summary

The material damage was estimated at 60 K Euros and concerned the thermal insulation of pipes, louvers protecting the reactor against atmospheric action, fire-proof concrete of the reactor frame and the instrumentation cables within a radius of 3 m. The blaze did not damage the reactor that was protected by a deflector. Operating losses stood at 300 k Euros.

Emergency action

The unit’s automatic alarms were triggered and the operator started the emergency shutdown, which isolated and depressurised the synthesis cycle.
Steam was sprayed on to the leak using mobile fire nozzles to extinguish the fire that was brought under control 55 minutes following its start.

Lesson Learnt

Corrective Measures

The following was implemented as corrective measures from the lesson learnt :
i) modification of tightening torque.
ii) improvement of leak collector on flange.
iii) nitrogen injection system in leak collector
iv) installation of vapour injectors to protect the reactor.

In-depth data

Release type
gas mixture
Involved substances (% vol)
H2 50%,
NH3 17%,
CH4,
N2
Probable IGNITION SOURCE
Flame type

References

Sources categories
ARIA
Reference & weblink

Event description in French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/32174/
(accessed September 2020)

Also uptaken from ARIA by US database H2TOOLS
https://h2tools.org/lessons/ignition-syngas-leak-ammonia-production-pla…
(accessed Sept 2025)