Syngas fire at an ammonia production plant

Event

Event ID
178
Quality
Description

The leak occurred at the ammonia reactor after a technical shutdown of 4 days. When the production was resumed and the syngas compressor restarted 14 hours later, a jet-fire occurred.
The Internal Operation Plan was launched and the fire immediately extinguished.

The cause of the gas release was a thermal dilatation difference between the joint and the reactor body. While the latter was still hot, the joint was cooled by the gas upon starting up the synthesis process. The high hydrogen concentration of the synthesis gas explains probably its spontaneous ignition.
An additional cause was the procedure of quickly and completely exposing synthesis loop components to air by systematically opening all sectional valves, even in the event of short-term shutdowns, increased the unit’s vulnerability to this type of incident.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
France
Date
Component involved
compressor / booster / pump (flange)
Failure mode
leak & ignition
Initiating cause
loss of tightness (thermal stress/cycling)
Root CAUSE analysis

The INITIATING cause was the loss of containment of the syngas due to thermal gradients between joint and reactor, and the spontaneous ignition of the gas.

Contributing cause was the shutdown procedure which opens all the valves, which exposes to air the whole ammonia synthesis loop.

In conclusion, root cause would be probably a deficiency in the design of the operation procedures

Root causes
Date entry in HIAD
28/02/2009

Facility

Application
Chemical industry
Sub-application
Ammonia production
Hydrogen supply chain stage
All components affected

Joint, inlect pipe, ammonia reactor

Process temperature range [C]
High temperature (100°C to 500°C)
Location type
Unknown
Location
industrial area
Operational condition
Pre-event occurrences

The ammonia production unit was stopped 4 days due to a technical incident. A syngas jet fire occurs when restarting the unit.
The shutdown prior to the accident stemmed from an incident on the turbo air compressor lubrication circuit of the NH3 unit that stopped the machine and nearly the entire unit.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Emergency action

The Internal Operation Plan was launched and the fire is immediately extinguished.

Lesson Learnt

Lesson Learnt

A rapid and total opening to the atmosphere of the reactor and of all the valves even for a short stop of the unit increase the likeliness of an incident.

Corrective Measures

The procedure was modified, by keeping the reactor pressurised by injecting nitrogen (80-100 bar) during short down periods and automatically closing the synthesis compressor connection in order to reduce the pressure decrease rate.

In-depth data

Release type
gas mixture (syngas)
Involved substances (% vol)
syngas
Probable IGNITION SOURCE
Flame type

References

Sources categories
ARIA
Reference & weblink

Description of the event in French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/30720/
(accessed September 2020)