Small leak at a hydrogen transfer hose

Event

Event ID
1137
Quality
Description

A leak occurred when transferring hydrogen from a trailer to the customer storage. The driver had just completed the pre-fill procedures and was starting to apply pressure to the fill hose, when he heard a leak coming from it. The driver immediately isolated the hose by shutting off the trailer manifold valve. The hose leaked for approximately 1 to 2 seconds. The driver terminated the fill process by using another hose and returned to his home facility.
The leaking transfer hose was inspected and a small leak was detected at the crimped fitting. The hose was purchased new in 2004, last tested in 8/2007 and was due again for test 8/2008.

Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
leak no ignition
Macro-region
North America
Country
United States
Date
Component involved
hose (trailer)
Failure mode
rupture, no ignition
Initiating cause
material degradation (generic)
Root CAUSE analysis

The INITIATING CAUSE was the leak of the flexible hose.
The ROOT CAUSE is unknown, the hose was regularly tested, unexpected ageing is the most plausible explanation.

Root causes
Date entry in HIAD
25/10/2024

Facility

Application
Hydrogen transport and distribution
Sub-application
CGH2 tube trailer
Hydrogen supply chain stage
All components affected

Hose

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
medium to high pressure (10 to 50 MPa)
Location type
Open
Location
industrial area
Operational condition
Pre-event occurrences

The driver had just completed the pre-fill procedures and was starting to apply pressure to the fill hose

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Currency
US$
Property loss (onsite)
0
Emergency action

The driver immediately isolated the hose by shutting off the trailer manifold valve.

Lesson Learnt

Lesson Learnt

Considering the small leak and very limited amount of hydrogen released, this incident is almost a near miss. According to the report, the failed component, a hose, had been regular inspected and tested, and the operator (the trailer driver) acted promptly and according to the procedure. A good example of how consequence of a leak can be controlled.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Released amount (kg)
0.3
Release temperature [°C]
25
Release pressure [MPa]
18
Probable IGNITION SOURCE

References

Sources categories
PHMSA
Reference & weblink

Incident I-2008070440 of the US Pipeline and Hazardous Materials Safety Administration PHMSA:
https://portal.phmsa.dot.gov/analytics/saw.dll?Portalpages&PortalPath=%…
(accessed September 2024)