Small leak from a CGH2 trailer

Event

Event ID
1145
Quality
Description

A driver found a small audible leak coming from the rear of the trailer compartment, while conducting in-trip visual walk-around inspection at a roadside. The driver set up perimeter around trailer using triangles and safety cones, contacted the trailer company to notify the leak and contacted local police department to inform of the situation. The company experts inspected found a leak coming from the neck valve threads one of the ten tubes. They decided to vent to atmosphere the hydrogen contained in that tube, connecting a portable vent stack. After having disabled the leaking valve, the trailer returned to facility for inspection and repair.

Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
leak no ignition
Macro-region
North America
Country
United States
Date
Component involved
joint/connection (threaded)
Failure mode
rupture, no ignition
Initiating cause
material degradation (generic)
Root CAUSE analysis

The INITIATING CAUSE was probably the loosening of a threaded connection of a valve. A possible technical explanation could be road vibrations, but other material ageing/degradation reasons cannot be excluded.

The ROOT CAUSE is not provided, however, an effective design should be able to take into account road vibrations on a road vehicle.

Root causes
Date entry in HIAD
25/10/2024

Facility

Application
Hydrogen transport and distribution
Sub-application
CGH2 tube trailer
Hydrogen supply chain stage
All components affected

Threaded Connection

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
medium to high pressure (10 to 50 MPa)
Location type
Open
Location
highway or similar
Operational condition
Description of the facility/unit/process/substances

DESCRIPTION OF THE UNIT
The trailer consisted of 10 tubes. The PHMSA source provides a value of released hydrogen of 11000 GCF (28 kg), which corresponds to the content of one tube. This results slightly lower than the nominal capacity of these tube, declared as 12500 GCF (318 kg)

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Currency
US$
Property loss (onsite)
0
Emergency action

The driver set up perimeter around trailer using triangles and safety cones, and notified local police and the company.
The company intervention team decided to depressurise the leaking tube by releasing its content to the atmosphere.

Lesson Learnt

Lesson Learnt

The mitigating measures worked well: (i) the regular inspection by drivers along the route, and (ii) the emergency handling by depressurising the leaking tube and releasing its content to the atmosphere.
The loosening of threaded connection due to road vibration is a common glitch. It is however unclear, in this event and similar event, how this could be avoided. Is the root cause related shortcoming when installing / maintaining the connections, or to unexpected road conditions during travel?

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Released amount (kg)
28
Release temperature [°C]
25
Release pressure [MPa]
17.4
Probable IGNITION SOURCE

References

Sources categories
PHMSA
Reference & weblink

Incident I-2015090569 of the US Pipeline and Hazardous Materials Safety Administration PHMSA:
https://portal.phmsa.dot.gov/analytics/saw.dll?Portalpages&PortalPath=%…
(accessed September 2024)