Small leak on CGH2 trailer

Event

Event ID
221
Quality
Description

A leak developed on a CGH2 tube trailer on the pigtail of one of the tube. The pigtail was cracked, possibly due to vibration. This trailer was tested the day before this incident and was found to be leak free.

The trailer consisted of 10 tube, and each tube has a pigitail. Trailers are tested for leaks every fill.

Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
leak no ignition
Macro-region
North America
Country
United States
Date
Component involved
piping (pigtail)
Failure mode
rupture, no ignition
Initiating cause
loss of tightness (road vibrations)
Root CAUSE analysis

The INITIATING CAUSE was the cracking of a pigtail, probably mechanical vibration from the road.
Different degradation modes could be excluded, because trailer components are tested for leak by every filling.
A possible ROOT CAUSE could be a shortcoming in the design, but also a non-further understood generic material failure.

Root causes
Date entry in HIAD
24/10/2024

Facility

Application
Hydrogen transport and distribution
Sub-application
CGH2 tube trailer
Hydrogen supply chain stage
All components affected

Hose

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
medium to high pressure (10 to 50 MPa)
Location type
Open
Location
highway or similar
Operational condition
Pre-event occurrences

The PHMSA report does not specify when the leak occurred. It is plausible to assume that it occurred when travelling or at the place of delivery.

Description of the facility/unit/process/substances

The trailer was a 10-tube trailer. Each tube had a capacity of almost 30 kg. Each tube had a pigtail attached to a main manifold.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Currency
US$
Property loss (onsite)
115
Post-event summary

The content of one tube was lost (approximately 30 kg). Material loss amounted to 115 US$.

Emergency action

The emergency actions are not reported. From the fact that the whole content of the tube was released, and from similar cases used as proxy, it can be reasonably assumed that the pigtail connection was isolated from the manifold, and the tube let leaking.

Lesson Learnt

Corrective Measures

The trailer manufacturer investigated a changed of design, by adding additional support to the main manifold, to reduce the amount of vibration to the pigtail. If this improvement was eventually implemented, is not reported.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Released amount (kg)
29.4
Release temperature [°C]
25
Probable IGNITION SOURCE

References

Sources categories
PHMSA
Reference & weblink

Incident I-1990060084 of the US Pipeline and Hazardous Materials Safety Administration PHMSA:
https://portal.phmsa.dot.gov/analytics/saw.dll?Portalpages&PortalPath=%…
(accessed September 2024)