Release without ignition from a refinery pipeline

Event

Event ID
893
Quality
Description

During an inspection tour, a worker detected a hydrogen leak in a refinery on a footbridge, 30 meters high. The exact location of the release was identified 4 days later, on a pipe covered by a thermal insulation. Workers equipped with Self Contained breathing Apparatus removed the insulation and found the leak at a reinforcing saddle.

The installation was shut down and put under nitrogen. Thickness measurements and radiographic checks were used to characterise the nature of the crack defect.
A leak sealing system was put in place, while awaiting the removal of the pipework for assessment during the next shutdown.

Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
leak no ignition
Macro-region
Europe
Country
France
Date
Component involved
pipe (generic)
Failure mode
rupture, no ignition
Initiating cause
unknown
Root CAUSE analysis

The INITIATING cause of the leak was a crack defect on the reinforcing saddle of a hydrogen pipe.
No detailed is known on the failure mechanism.

Root causes
Date entry in HIAD
01/01/2018

Facility

Application
Petrochemical industry
Sub-application
Unspecified refinery process
Hydrogen supply chain stage
All components affected

hydrogen pipeline

Location type
Open
Location
industrial area
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Emergency action

The installation is shut down and put under nitrogen. A leak sealing system is put in place, allowing for further operation till the next shutdown when the pipework will be replaced.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Probable IGNITION SOURCE

References

Sources categories
ARIA
Reference & weblink

ARIA event no. 55163