Skip to main content
Clean Hydrogen Partnership

Release from hydrogen cylinders storage of a chemical plant

Event

Event ID
930
Quality
Description

A leak occurred on a rack containing 12 cylinders of hydrogen (50 l at 200 bar each) delivered by a lorry inside the fenced storage area of a bulb manufacturing plant.

The plant’s safety manager closed access to the area, had the other lorry drivers on the site cut off their ignitions, and made them evacuate. The firefighters tested the air with an explosimeter and stopped the leak by closing the gate valve located on the outside of the rack. The valve was used to transfer hydrogen from the cylinders to their points of use.

The rack had been delivered by a crane lorry. Each of the top four corners of the rack was fitted with a steel ring that was used to lift the rack off the lorry. The gate valve was opened when one of the four lifting chains used to lift the rack off the lorry accidentally wrapped around it.

Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
leak no ignition
Macro-region
Europe
Country
France
Date
Component involved
valve (shut-off)
Failure mode
rupture, no ignition
Initiating cause
impact, rollover, crash
Root CAUSE analysis

INITIATING cause was the accidental opening of the main hydrogen valve during unloading of the lorry.

Root causes
Date entry in HIAD
01/01/2018

Facility

Application
Hydrogen transport and distribution
Sub-application
CGH2 cylinders truck
Hydrogen supply chain stage
All components affected

cylinders

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
medium to high pressure (10 to 50 MPa)
Location type
Open
Location
industrial area
Operational condition
Pre-event occurrences

The lorry had been delivered to destination and the unloading of the rack of hydrogen cylinders was ongoing by means of the lorry crane

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Post-event summary

The ARIA report (see references) does not provide quantitative assessment of the amount of hydrogen released.

Emergency action

13:30 Hydrogen release started - The plant’s safety manager closed access to the area, had the other lorry drivers on the site cut off their ignitions, and commanded an evacuation.
The firefighters tested the air with an explosimeter and stopped the leak by closing the gate valve.
15:00 The firefighters left and the plant resumed normal operations.

Lesson Learnt

Corrective Measures

According to the ARIA report (see references), the operator took the following two corrective measures:
i) stopped deliveries of this type of rack ,
ii) replaced it by one with 16 cylinders, fitted with a cover and a central lifting ring.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Release pressure [MPa]
20
Probable IGNITION SOURCE

References

Sources categories
ARIA
Reference & weblink

Event description in the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/44315/