Skip to main content
Clean Hydrogen Partnership

Release of a flammable mixture from a compressor

Event

Event ID
351
Quality
Description

Following the breakdown of a piston rod, a mixture of hydrogen and light hydrocarbons was released from the fresh hydrogen compressor of an oil refinery.
The rod broke down because of stress corrosion. The stress exerted on the rod was significantly increased by the looseness of the piston fixing point.
The gas mixture ignited, also igniting the lubricating oil and other items in the room.
Some 1,500 kg of hydrogen gas and a few hundred litres of lubricating oil were estimated to have been burned.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
Finland
Date
Component involved
compressor / booster / pump (piston)
Failure mode
rupture & ignition
Initiating cause
material degradation (stress-corrosion)
Root CAUSE analysis

The INITIATING CAUSE was the breaking rupture a rod due to stress corrosion. The stress exerted on the rod was significantly increased by the looseness of the piston fixing point.

The ROOT CAUSE, although not provided by the source, could be identified in shortcomings in service and maintenance. Nevertheless, also a design error cannot be excluded.

Root causes
Date entry in HIAD
28/02/2009

Facility

Application
Petrochemical industry
Sub-application
Unspecified refinery process
Hydrogen supply chain stage
All components affected

rod,
piston,
gas compressor

Location type
Open
Location
industrial area
Operational condition
Pre-event occurrences

A piston rod broke down in a hydrogen compressor of an oil refinery. The rod broke down because of stress corrosion. The stress exerted on the rod was significantly increased by the looseness of the piston fixing point.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Post-event summary

Some 1,500 kg of hydrogen gas and a few hundred litres of lubricating oil were estimated to have been burned.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Released amount (kg)
1500
Probable IGNITION SOURCE

References

Sources categories
Unknown
Reference & weblink

Source lost