Event
- Event ID
- 812
- Quality
- Description
Hydrogen leak occurred during a delivery of hydrogen at an automotive supplier. Rescue deployed a curtain of water and evacuated 82 employees from several companies within a radius of 50 m. The hydrogen installation was then purged. The intervention ended at 4 hours later. The accident was caused by a rupture of a connection element (lyre) between the hydrogen bottle in the delivery truck and the receiving tank.
- Event Initiating system
- Classification of the physical effects
- Unignited Hydrogen Release
- Nature of the consequences
- leak no ignition
- Macro-region
- Europe
- Country
- France
- Date
- Component involved
- joint/connection (lyre)
- Failure mode
- rupture, no ignition
- Initiating cause
- material degradation (generic)
- Root CAUSE analysis
A rupture of a connection element between the hydrogen bottle in the delivery truck and the receiving tank
- Root causes
- Unknown
- Date entry in HIAD
- 01/01/2020
Facility
- Application
- Hydrogen transport and distribution
- Sub-application
- CGH2 tube trailer
- Hydrogen supply chain stage
- All components affected
Connection between hydrogen delivery truck and a stationary storage tank
- Process temperature range [C]
- ambient temperature (-50°C to +50°C)
- Process pressure range [MPa]
- medium to high pressure (10 to 50 MPa)
- Location type
- Open
- Location
- populated area
- Operational condition
- Description of the facility/unit/process/substances
DESCRIPTION OF THE FAILED COMPONENT
A lyre is typically a single piece of metal tubing (usually copper or stainless steel) that has been mechanically bent into a loop or "S" shape. In this sense, it differs from a hose, which is a composite flexible tubing, consisting of more layers, and designed to be moved and bent repeatedly.
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
- Emergency action
Rescue deployed a curtain of water and evacuated 82 employees from several companies within a radius of 50 m. The hydrogen installation was then purged. The intervention ended at 4 pm.
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Release temperature [°C]
- 25
- Probable IGNITION SOURCE
References
- Sources categories
- ARIA
- Reference & weblink
ARIA data base
event no. 43180