Event

Event ID
765
Quality
Description

A leak occurred on a line connecting the hot separator to the cold separator of a refinery diesel desulphurization.
The alert was given by the activation of the fixed H2S detector.
The 30 bar pressure line contained essentially hydrogen with a high concentration of H2S. The operators stopped the unit and isolated the leak in about ten minutes. The line was pierced at a bend at an angle of 135, following a bend at an angle of 90 degrees. The accident investigation showed that the presence of the elbows resulted in turbulence which created a localized depression: this configuration favoured the formation of deposits (in particular during the stops of the water wash pump).

Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
leak no ignition
Macro-region
Europe
Country
France
Date
Component involved
pipe (bend)
Failure mode
leak, no ignition
Initiating cause
material degradation (internal corrosion / erosion)
Root CAUSE analysis

The INITIATING CAUSE was puncturing of the H2 pipe due to deposition of corrosive substance at the pipe bends.
An inspection of the 90-degree elbow was performed by the site inspection department, but not the one with the 135-degree elbow.
The ROOT CAUSE could be a combination of shortcoming in design (favouring local corrosion) and of a lack of thorough inspection.

Root causes
Date entry in HIAD
01/01/2020

Facility

Application
Petrochemical industry
Sub-application
Hydrodesulphurisation process
Hydrogen supply chain stage
All components affected

process gas pipe

Process temperature range [C]
Above ambient temperature (50°C to 100°C)
Process pressure range [MPa]
medium pressure (2 to 10 MPa)
Location type
Unknown
Location
industrial area
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Post-event summary

The operators stopped the unit and isolated the leak in about ten minutes.

Emergency action

The alert was given by the activation of the fixed H2S detector.
The operators stopped the unit and isolated the leak in about ten minutes.

In-depth data

Release type
gas mixture
Involved substances (% vol)
H2,
H2S
Release temperature [°C]
25
Release pressure [MPa]
3
Probable IGNITION SOURCE

References

Sources categories
ARIA
Reference & weblink

ARIA data base
event no. 23175:
https://www.aria.developpement-durable.gouv.fr/accident/23175/
(accessed July 2024)