Release and fire from a hydrogen pipeline

Event

Event ID
1060
Quality
Description

An in-line inspection of the hydrogen pipeline was being conducted and prior to the last run of the in-line inspection tool (magnetic flux leakage), hydrogen gas was released and ignited from a blind flange connection failure on a temporary separator filter installed at the receiver site. The fire was immediately identified by on-site personnel. There were no injuries. The pipeline section was isolated and de-pressurised to the facility flare. Local emergency responders were dispatched and contained and extinguished the fire. The fire affected the station piping and equipment in the surrounding area. Repairs and/or replacement of affected piping and equipment were completed and re-commissioned.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
North America
Country
United States
Date
Component involved
pipeline (flange)
Failure mode
rupture
Initiating cause
unknown
Root CAUSE analysis

Failure of a blind flange connection, which had been temporarily installed to allow for an in-line inspection. According to the PHMSA report, there was no reason for an investigation, because there was no indication that the actions of the controller(s) or control room were the cause of, or a contributing factor to, the incident. The most logic explanation of the failure would then be a wrong installation of the temporary flange.  

Root causes
Date entry in HIAD
01/07/2024

Facility

Application
Hydrogen transport and distribution
Sub-application
H2 delivery to customers
Hydrogen supply chain stage
All components affected

H2 pipeline

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
medium to high pressure (10 to 50 MPa)
Location type
Open
Location
countryside or desert
Operational condition
Pre-event occurrences

The incident occurred during an inline inspection.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Currency
US$
Property loss (onsite)
1.451.027
Emergency action

The pipeline section was isolated and de-pressurised to the facility flare. Local emergency responders were dispatched and contained and extinguished the fire. The fire affected the station piping and equipment in the surrounding area.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Released amount (kg)
1974
Release temperature [°C]
25
Release pressure [MPa]
10.2
Probable IGNITION SOURCE

References

Sources categories
PHMSA
Reference & weblink

US Pipeline and Hazardous Materials Safety Administration PHMSA: https://www.phmsa.dot.gov/safety-reports/pipeline-failure-investigation-reports