Skip to main content
Clean Hydrogen Partnership

Mix-up of hydrogen and oxygen in a gas production plant

Event

Event ID
1093
Quality
Description

This near-miss occurred at a company producing compressed gas bottles according to customers requests. When preparing a gas mixture containing oxygen and nitrogen, by mistake hydrogen was added, instead of nitrogen. The gas lines did not have clear labelling. The mistake was discovered during analysis, when a small gas sample (less than 5 ml) ignited during flashing.

Event Initiating system
Classification of the physical effects
No Hydrogen Release
Nature of the consequences
Macro-region
Europe
Country
Germany
Date
Component involved
CGH2 cylinder(s)
Failure mode
n.a.
Initiating cause
wrong operation
Root CAUSE analysis

The INITIATING CAUSE was a human error in connecting the wrong pipeline.
A contributing CAUSE was the lack of clear labelling of the pipelines gases.
The root CAUSE could be attributed to management, which did not consider the risk of gas mixing up and did not adopted preventing measures such as different connector for different (incompatible) gases.

Root causes
Date entry in HIAD
01/07/2024

Facility

Application
Chemical industry
Sub-application
industrial gases production
Hydrogen supply chain stage
All components affected

compresed gas mixture bottle

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Location type
Confined
Location
industrial area
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Property loss (onsite)
0
Post-event summary

The mixed quantities were small: 0.07 kg hydrogen and 0.33 kg oxygen.

Emergency action

The building was evacuated.
The bottles containing the potentially explosive mixture were blown up by the police.

Lesson Learnt

Corrective Measures

The following measures were adopted:
(1) Clear marking of each gas pipeline , visible at working height
(2) Clear labelling of the filling valves with the respective gas type-specific colours and labels
(3) Installation of a protective flap as a mechanical locking of the filling valve
(4) Separate and gas type-specific connections

In-depth data

Release type
gas mixture
Involved substances (% vol)
H2 (0.07 kg),
O2(0.33 kg)
Released amount (kg)
0.07
Release temperature [°C]
25
Probable IGNITION SOURCE

References

Sources categories
ZEMA
Reference & weblink

Event from German database ZEMA
https://www.infosis.uba.de/index.php/de/site/12981/zema/index/3297.html
(accessed December 2023)

Event from German database ZEMA - trnslation
https://www.infosis.uba.de/index.php/de/site/12981/zema/index/3297.html