Skip to main content
Clean Hydrogen Partnership

Leakage in an ammonia and fertilisers plant

Event

Event ID
807
Quality
Description

A hydrogen leakage occurred in the ammonia production facility of a plant manufacturing nitrogen products and fertilisers (classified SEVESO high threshold).
It was detected by an operator in charge of safety checks, by the noise and by his portable gas detector. After confirming the leak, the operator stopped the piping (30 bar) to repair it. The ammonia facility was also partially shut down. The operator closed the section at the origin of the leak by installing a threaded and welded plug.

Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
leak no ignition
Macro-region
Europe
Country
France
Date
Component involved
pipe (bend)
Failure mode
rupture, no ignition
Initiating cause
material degradation (external corrosion)
Root CAUSE analysis

The leak was due to corrosion under insulation on a DN50 dead arm: a 90 ° elbow punctured on DN400 piping. The control plan for the piping was not foreseeing the removal of the insulation of this section.

Root causes
Date entry in HIAD
01/01/2020

Facility

Application
Chemical industry
Sub-application
Fertilisers production
Hydrogen supply chain stage
All components affected

ammonia synthesis reactor, hydrogen pipe

Process temperature range [C]
High temperature (100°C to 500°C)
Location type
Confined
Location
industrial area
Operational condition
Pre-event occurrences

A operator was carrying out safety checks in the ammonia workshop.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Post-event summary

The ammonia workshop was partially shut down.

Official legal action

The Classified Installations Inspectorate requests the RIS (Recognized Inspection Service) to review these plans to check sensitive areas of piping throughout the plant.

Emergency action

After confirming the leak, the operator stopped the piping (30 bar) to repair it. The ammonia workshop was also partially shut down. The operator closed the section at the origin of the leak by installing a threaded and welded plug.

Lesson Learnt

Corrective Measures

The Inspectorate for the Seveso-classified plants requested the RIS (Recognized Inspection Service) to review the inspection plans and to check sensitive areas of piping throughout the plant.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Probable IGNITION SOURCE

References

Sources categories
ARIA
Reference & weblink

ARIA data base
event no. 51978