Leak from a hydrogen compressor

Event

Event ID
1148
Quality
Description

The incident occurred at a hydrogen compression facility, due to a leaking connection. The hydrogen was released through the pressure relief inertised line. It ignited when mixing with air at the exit of the line.
The system was brought into a safe operating condition, the company the fire brigade, the superiors and the crisis team were informed. The flame was extinguished by switching off the system or the hydrogen supply.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
Germany
Date
Component involved
compressor / booster / pump (valve)
Failure mode
rupture & ignition
Initiating cause
unknown
Root CAUSE analysis

The INITIATING CAUSE was a leak on a fitting of a pressure relief device.
By analysis the corrective measures taken, the ROOT CAUSE could be possibly assigned to shortcoming in the procedures related to inspections of the joints and to the design of the venting lines (probably to avoid mixing hydrogen and air in the vent duct).

Root causes
Date entry in HIAD
25/10/2024

Facility

Application
Chemical industry
Sub-application
gas delivery company
Hydrogen supply chain stage
All components affected

fitting,
PRD,
vent line

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Location type
Open
Location
industrial area
Operational condition
Pre-event occurrences

ZEMA reports that the regeneration process was running under normal conditions.
A similar events had happened September 25, 2017, when a flame broke out on a relief line in the area of the low-temperature adsorber used for the hydrogen purification.

Description of the facility/unit/process/substances

DESCRIPTION OF THE UNIT
It appears that the affected compressor was part of a system containing also a regeneration step. Unclear is of it relates to the regeneration of a catalyst by means of hydrogen or to purification of hydrogen.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Property loss (onsite)
0
Post-event summary

No injury, no material damage: the discharge line was constructed according to internal standards and was not damaged by the fire.

Emergency action

The area was cordoned off and the plant was shut down.
After that, the relief line was monitored by an infrared thermometer and the line was briefly cooled with water.

Lesson Learnt

Corrective Measures

• The purging of all identical relief lines was improved
• All valves were replaced
• The procedure managing the inspection of the valves was modified by increasing inspection frequency
• The Regeneration process procedure was extended by including leak testing involving an approval by a supervisor.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Released amount (kg)
3.6
Release temperature [°C]
25
Probable IGNITION SOURCE

References

Sources categories
ZEMA