Leak from a CGH2 tube trailer

Event

Event ID
288
Quality
Description

A tube trailer carrying compressed hydrogen was travelling along a city road, when the drivers heard an abnormal sound from behind. They stopped and discovered that hydrogen was leaking from the threaded joint of a pipe connecting all the tubes to the manifold. They tightened the joint, but the leak did not stop, therefore it was decided to transfer hydrogen to another tube trailer.
The reason of the leak was the O-ring of the joint, which did not fit properly. All tube trailers of the same type were modified by installing a valve to each of the tubes.

Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
leak no ignition
Macro-region
Asia
Country
Japan
Date
Component involved
joint/connection (gasket)
Failure mode
leak, no ignition
Initiating cause
wrong component
Root CAUSE analysis

The INITIATING CAUSE was a defective O-ring causing a leak on a joint.
According to the KHK report, the was an inspection failure, which had not been able to identify the wrong O-ring and the ensure tightness the joint before departure. Since the leak was heard only when travelling, road vibration could have been a contributing factor. Since there was no possibility to isolate the tubes from the general manifold, the fundamental ROOT CAUSE is a shortcoming in design, which did not take into account all possible accidental scenarios.

Root causes
Date entry in HIAD
30/08/2025

Facility

Application
Hydrogen transport and distribution
Sub-application
CGH2 tube trailer
Hydrogen supply chain stage
All components affected

O-ring, threaded joint

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
medium to high pressure (10 to 50 MPa)
Location type
Open
Location
populated area
Operational condition
Pre-event occurrences

There were 22 long tubes on the trailer

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Post-event summary

Since the O-ring was defective and therewas no possibility to isolate the tubes from the common manifold, it was decided to transfer hydrogen to another tube trailer.

Emergency action

The drivers tightened the joint, but the leak did not stop, therefore it was decided to transfer hydrogen to another tube trailer.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Probable IGNITION SOURCE

References

Sources categories
KHK
Reference & weblink

High Pressure Gas Accident Cases Database of the KHK (High Pressure Gas Safety Association):
https://www.khk.or.jp/public_information/incident_investigation/hpg_inc…
(accessed May 2025)