Leak from a CGH2 trailer

Event

Event ID
233
Quality
Description

A CGH2 trailer-tractor arrived at a customer’s site for delivery. When stopping at gate and coming out of the cab, the driver noticed a noise coming from the rear of the trailer. The driver opened the rear cabinet door and found a pigtail line cracked. Hydrogen was leaking from the shut-off valve and to a minor extent from the crack. The emergency team on the customer site washed the rear of cabinet until the delivery company expert arrived on the scene. The expert cut and crimped the cracked line. He then placed a block in the valve to secure the leaking tube. The driver did not execute the delivery and returned the full trailer to the home site without incident.
The investigation revealed that road vibration had caused the line to the pigtail to crack. The pigtail and valve seat were replaced and the trailer was brought back to service.

Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
leak no ignition
Macro-region
North America
Country
United States
Date
Component involved
piping (pigtail)
Failure mode
rupture, no ignition
Initiating cause
loss of tightness (road vibrations)
Root CAUSE analysis

The INITIATING CAUSE were road travel vibrations damaging a pigtail connection in the trailer pressure control cabinet.

The ROOT CAUSE was shortcoming in the design, and possibly also in the installation of the pigtail – valve connection.

Root causes
Date entry in HIAD
25/10/2024

Facility

Application
Hydrogen transport and distribution
Sub-application
CGH2 tube trailer
Hydrogen supply chain stage
All components affected

pigtail, valve

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
medium to high pressure (10 to 50 MPa)
Location type
Open
Location
industrial area
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Currency
US$
Property loss (onsite)
52
Emergency action

The emergency tem on the customer site washed the rear of cabinet until the delivery company expert arrived on the scene. The expert cut and crimped the cracked line. He then placed a block in the valve to secure the leaking tube.

Lesson Learnt

Lesson Learnt

Simulation studies have shown that a leak inside the trailer control cabinet could cause the formation of a flammable atmosphere. In this case, it is probable that the hydrogen flow of the leak was very small and allowing dispersion in place of formation of a flammable gas mixture.
Nevertheless, the cabinet should be handled as an explosive atmosphere zone and preventing/mitigating measures have to be taken into account in its design. Moreover, a procedure should be in place, which allow the driver to understand what is happening in the cabinet without having to open manually the cabinet door, an action which could provide the ignition energy to a hydrogen-air mixture.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Released amount (kg)
26.5
Release temperature [°C]
25
Release pressure [MPa]
18
Probable IGNITION SOURCE

References

Sources categories
PHMSA
Reference & weblink

Incident I-1991060202 of the US Pipeline and Hazardous Materials Safety Administration PHMSA:
https://portal.phmsa.dot.gov/analytics/saw.dll?Portalpages&PortalPath=%…
(accessed September 2024)