Event
- Event ID
- 937
- Quality
- Description
The fire took place during maintenance works in one out of the three gas extractors of the coke process line. Main cause was the displacement of a flange which allowed the entrance of flammable mixture gas (methane, carbon monoxide hydrogen and benzene) which ignited probably due to electrostatic spark.
According to the ARIA report total quantity of gas released was 62 400 m³, consisting of 11,7 t CH4, 0,98 t C6H6, 5,1 t CO and 3,4 t H2.During maintenance works, gas extractors were usually isolated and kept under continuous flow of N2. However, in this case, N2 pressure seemed to be not enough to avoid the entrance of flammable gas.
- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- fire
- Macro-region
- Europe
- Country
- France
- Date
- Component involved
- valve (generic)
- Failure mode
- rupture & ignition
- Initiating cause
- inadequate or no purge
- Root CAUSE analysis
INITIATING cause was probably the inert gas pressure insufficient to prevent the entrance of the flammable mixture.
- Root causes
- Date entry in HIAD
- 01/01/2018
Facility
- Application
- Steel and metals industry
- Sub-application
- Steel metallurgy
- Hydrogen supply chain stage
- All components affected
coke process line, flange
- Process temperature range [C]
- ambient temperature (-50°C to +50°C)
- Process pressure range [MPa]
- unknown
- Location type
- Unknown
- Location
- industrial area
- Operational condition
- Pre-event occurrences
The event took place during maintenance of a gas extractor, which has a diameter of 1400 mm. During maintenance, the line was isolated from gas stream using two flanges, one before and another one after the equipment.
The accident occurred after maintenance works have finished and the gas extractor was been prepared again for operation: the procedure required as final steps the closing of the downstream flange and then the opening of the inlet one. The leak occurred immediately after the opening of the inlet flange.
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 2
- Post-event summary
Damage to property: on-site more than 2 millions of Euros, off-site more than 0.5M millions of Euros. The released susbtances were:
H2 3.4 t
CO 5.1 t
CH4 11.7 t
C6H6 0.98 t- Emergency action
The employers have been evacuated. The site fire brigade put the extractor under nitrogen and cooled it by water jets. The fire and the leak are stopped after approximately 1 hour.
Lesson Learnt
- Corrective Measures
The operator has foreseen to improve the procedure for the isolation of the section at the following maintenance and to review the risk assessment.
In-depth data
- Release type
- gas mixture
- Involved substances (% vol)
- H2 3.4 t
CO 5.1 t
CH4 11.7 t
C6H6 0.98 t - Released amount (kg)
- 3400000
- Probable IGNITION SOURCE
References
- Sources categories
- eMARS
- Reference & weblink
Event description in the European database eMARS
https://emars.jrc.ec.europa.eu/en/eMARS/accident/view/2c958f15-e9a3-11e…
(accessed September 2020)Radio RPA online news:
https://www.radiorpa.fr/fuite-de-gaz-enflamm%C3%A9e-2-bless%C3%A9s-%C3%…
(accessed July 2024)Online news Le Port de Saint Louis: company communication
ARIA incident No. 1706