Hydrogen fire at a gas production facility

Event

Event ID
989
Quality
Description

A leak occurred while loading a trailer carrying hydrogen gas cylinders. The trailer was loaded with 4 bundles of 60 cylinders at 200 bar which were beeing refilled.
The leak was heard, and an employee closed the supply valve but the leak ignited and reached the trailer's tires. The vehicle caught fire, causing a plume of black smoke visible from a distance. The plant operator evacuated the personnel and activated the emergency response plan. The water sprayers in the filling station and the site was shut down. The firemen and the operator prevented the spread of the fire beyond the 3 other trailers parked at the loading station. After approximately 2 hours, the firemen brought the fire under control.
Early in the morning of the day after approximately 10 hours since the extinction of the fire, the fire broke out again on the tires of a semi-trailer. The firefighters used twice the firefighting flow of the first phase. After 5 hours , the firefighters finished extinguishing the semi-trailer. They checked that there were no hot spots using a thermal camera. The operator called off the emergency plan.
There were no injuries but the material consequences of the fire were severe: 11 cylinders within one bundle bursted and two adjacent hydrogen trailers partially burnt.
The plant operator activated a post-accident crisis unit to study how to empty the trailers from the remaining hydrogen and to purge them.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
France
Date
Component involved
joint/connection (pigtail)
Failure mode
rupture & ignition
Initiating cause
unknown
Root CAUSE analysis

INITIATING CAUSE: several potential sources of hydrogen leakage were identified at the level of the trailer: either on a connection loop between a cylinder and a manifold, or on the manifold, or on a cylinder. Most probably, a small leak on fitting caused a rupture of a pigtail which induced a hydrogen jet fire, igniting the tyres and causing the cylinders to burst.

ROOT CAUSE:
(i) shortcoming in procedures for maintenance and inspection of the trailer/bundles design.
(ii) lack of effective prevention and mitigation measures during filling, probably related to shortcoming of the risk assessment

Root causes
Date entry in HIAD
01/01/2024

Facility

Application
Hydrogen transport and distribution
Sub-application
CGH2 cylinders truck
Hydrogen supply chain stage
All components affected

semi-trailer, hydrogen cylinders

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
medium to high pressure (10 to 50 MPa)
Location type
Open
Location
industrial area
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Post-event summary

Three semi-trailers showed significant destruction, resulting in an economic loss of 488 k€. The hydrogen conditioning installations required a repair estimated at 50 k€.
The site was shut down and production was relocated.

The study of the smoke plume concluded that there was no toxic effect in the vicinity of the site. The analysis of the extinguishing water shows a quality allowing its discharge into the natural environment.

Emergency action

During the first fire, the fire brigade used water.
During the fighting of the second fire, it used first twice the firefighting flow of the first phase. The extinguishing water was collected in a retention basin designed for this purpose, but it reached its maximum filling level.
Later one, to limit the amount of water, the firemen use foam. To reduce the level of water in the basin, the operator opens its water discharge to the environment at a low rate. Firefighters set up a filtering system for the hydrocarbons. The water from the basin is then returned to the fire reserve.
Finally, a thermal camera was used to ensure that there were no hot spots left.

Lesson Learnt

Corrective Measures

Pending the outcome of the investigation, the plant operator has removed from the company's fleet a batch of semi-trailers of the same model as the one involved.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Probable IGNITION SOURCE

References

Sources categories
ARIA
Reference & weblink

Event description no 55834 in the French database ARIA (accessed October 2021)

A detailed analysis was presented by Ruban et al. at the 2023 Center for Hydrogen Safety Europe Conference
The resentation is behind a paywall, but the abstract is available on line:
https://proceedings.aiche.org/conferences/center-hydrogen-safety-confer…
(accessed January 2025)

News of 30 July of the La Voix du Nord
https://www.lavoixdunord.fr/845839/article/2020-07-30/douai-incendie-en…
(accessed November 2021)