Event
- Event ID
- 936
- Quality
- Description
Hydrogen fire at a chlorine chemical production plant (Seveso-classified)
Hydrogen ignited in a chlorine electrolyser unit. The facility was shutdown when the incident occured. The staff of the unit, present on site, triggered the fire alarm and put the installations in a safe state. The fire was extinguished after the start of the intervention of the internal fire brigade.
According to the ARIA report, a variation in electrolyser pressure was caused by the shutdown of a tank due to the malfunction of its level detection gauge. This variation caused, on one single cell, the tearing of the flexible PTFE belt whose role is to protect the cell from pressure shocks. This tearing resulted in the release of a small amount of hydrogen that spontaneously ignited. The other belts did not suffer, suggesting a structural weakness of the damaged one. These belts are regularly monitored by the operator, but their packaging during transport may have plaid a role.
- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- fire
- Macro-region
- Europe
- Country
- France
- Date
- Component involved
- electrolytic cell
- Failure mode
- rupture & ignition
- Initiating cause
- malfunctioning (electrolyser, cross-over)
- Root CAUSE analysis
INITIATING CAUSE was the loss of confinement on a cell of the chlorine electrolyser, due to an operation on a neighbouring system.
- Root causes
- Unknown
- Date entry in HIAD
- 01/01/2018
Facility
- Application
- Chemical industry
- Sub-application
- Chlorine production
- Hydrogen supply chain stage
- All components affected
electrolyser cells
- Process temperature range [C]
- ambient temperature (-50°C to +50°C)
- Location type
- Unknown
- Location
- industrial area
- Operational condition
- Pre-event occurrences
The unit was shutdown.
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
Lesson Learnt
- Lesson Learnt
The ARIA report (see reference) does not mention any lesson learnt.
One possible corrective action, could be an improved estimation of the consequences of modifications made to part of system, for the rest of the system .
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Release temperature [°C]
- 25
- Probable IGNITION SOURCE
References
- Sources categories
- ARIA
- Reference & weblink
Event description in the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/43523/
(accessed September 2020)