Skip to main content
Clean Hydrogen Partnership

Hydrogen fire at a chlorine chemical production plant

Event

Event ID
936
Quality
Description

Hydrogen fire at a chlorine chemical production plant (Seveso-classified)

Hydrogen ignited in a chlorine electrolyser unit. The facility was shutdown when the incident occured. The staff of the unit, present on site, triggered the fire alarm and put the installations in a safe state. The fire was extinguished after the start of the intervention of the internal fire brigade.

According to the ARIA report, a variation in electrolyser pressure was caused by the shutdown of a tank due to the malfunction of its level detection gauge. This variation caused, on one single cell, the tearing of the flexible PTFE belt whose role is to protect the cell from pressure shocks. This tearing resulted in the release of a small amount of hydrogen that spontaneously ignited. The other belts did not suffer, suggesting a structural weakness of the damaged one. These belts are regularly monitored by the operator, but their packaging during transport may have plaid a role.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
France
Date
Component involved
electrolytic cell
Failure mode
rupture & ignition
Initiating cause
malfunctioning (electrolyser, cross-over)
Root CAUSE analysis

INITIATING CAUSE was the loss of confinement on a cell of the chlorine electrolyser, due to an operation on a neighbouring system.

Root causes
Unknown
Date entry in HIAD
01/01/2018

Facility

Application
Chemical industry
Sub-application
Chlorine production
Hydrogen supply chain stage
All components affected

electrolyser cells

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Location type
Unknown
Location
industrial area
Operational condition
Pre-event occurrences

The unit was shutdown.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0

Lesson Learnt

Lesson Learnt

The ARIA report (see reference) does not mention any lesson learnt.
One possible corrective action, could be an improved estimation of the consequences of modifications made to part of system, for the rest of the system .

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Probable IGNITION SOURCE

References

Sources categories
ARIA
Reference & weblink

Event description in the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/43523/
(accessed September 2020)