Skip to main content
Clean Hydrogen Partnership

Hydrogen fire at a chemical plant

Event

Event ID
919
Quality
Description

The event affected a unit producing ferric chloride (FeCl2) in a SEVESO-classified chemical plant. A fire broke out in the acid etching tank of the unit. In this tank a reaction between iron metal and hydrochloric acid in solution was carried out, having as reaction product ferrous chloride and hydrogen. The hydrogen generated was swept away by a large supply air fan to maintain the gaseous sky of the tank below the low explosion/flammability level of hydrogen in air.

A few days after the accident, the operator opened and analysed the tank to determine the origin of the fire. The reason for the fire was found to be a slow combustion of hydrogen, initiated during the loading of metal. Despite the air circulation, hydrogen accumulated at the bottom of the tank due to its overfilling. The fire then spread outside the tank through the roof opening caused by the degradation of the hydrogen detector and by melting the blast doors. The fire was then alimented by the plastic components of the equipment and the surrounding piping, as well as by the oil from the hydraulic pistons of the roof door of the tank.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
France
Date
Component involved
reactor / oven / furnace / test chamber
Failure mode
rupture & ignition
Initiating cause
wrong operation
Root CAUSE analysis

The INITIATING CAUSE was the development of hydrogen – air flammable mixture inside the tank, which ignited by a non-reported source.
The hydrogen enrichment was caused by the overloading of the tank with iron, which created internal zones not affected by the ventilation.

Considering also the corrective actions described in the ARIA report, the ROOT CAUSE was probably inadequate safety design and operation.

Root causes
Date entry in HIAD
01/01/2018

Facility

Application
Chemical industry
Sub-application
Inorganic chemicals products
Hydrogen supply chain stage
All components affected

reaction tank, production of iron chloride (FeCl2)

Location type
Semiconfined
Location
industrial area
Operational condition
Description of the facility/unit/process/substances

DESCRIPTION OF THE PROCESS
The stoichiometric reaction at the basis of the process is: Fe + 2 HCl → FeCl2 + H2

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Post-event summary

No injuries. The unit restarted 6 months after the accident.
Damage to the tank upper parts, hydrogen detector and doors

Emergency action

23:40 The Plant safety emergency plan is initiated .
23:53 The fire is reducing
00:50 Despite a small residual still persisting, the fire is extinguished and the reaction unit stopped.
00:45 The emergency plan is called off.
01:25 The leak is sopped.

Lesson Learnt

Lesson Learnt

The accident suggests that the operative procedure related to the loading of the materials and the preventive measures (hydrogen detection) were inadequate.

Corrective Measures

According to the ARIA report (see references), the operator updates the risk analysis of this unit and reinforces controls on the level of scrap metal in the tank and analyses of hydrochloric acid.
It also added safety features on the low air sweep rate and high temperature in the tank and lowers the alarm threshold of the hydrogen analyser.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Probable IGNITION SOURCE

References

Sources categories
ARIA
Reference & weblink

Event 49915 of the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/49915/
(accessed September 2020)