Event
- Event ID
- 969
- Quality
- Description
The accident occurred at a distillate dewaxing Unit (MDDW) of the refinery, during the operation of regeneration of the catalyst. To perform the regeneration, both temperature and pressure had to be increased from the the values used for production. After approximately six hours after having reached the correct regeneration conditions, a 10 inches pipe at the bottom to one of the two reactor experienced a guillotine break, and hot gas was released from both ends. The gas released consisted of 81% of hydrogen, 9.5% of methane and some light hydrocarbons. It rapidly ignited (0.7 sec), causing an explosion. A shock wave from the resulting explosion expanded through the adjacent neighbourhood, causing varied degrees of blast damage to residential homes. The ensuing flash fire spread up to 230 feet west of the tank farm.
- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Macro-region
- North America
- Country
- United States
- Date
- Component involved
- pipe (generic)
- Failure mode
- rupture & ignition
- Initiating cause
- material degradation (internal corrosion / erosion)
- Root CAUSE analysis
The INITIATING cause of the accident was the corrosion of pipe, inducing thinning of the pipe wall. The corrosion went uninspected for years.
According the CBS report, the metallurgical analysis identified the same kind of suffixation corrosion already found in accidents in other plants; sulphur compounds in the process stream corroded a steel piping segment, causing the pipe walls to become severely thin. While sulfidation is a well-known damage mechanism at refineries that requires regular inspection and monitoring, the segment that failed has no record of ever being inspected.
This suggests a ROOT CAUSE related to lack of effective maintenance and inspection procedures and to management shortcoming.- Root causes
- Date entry in HIAD
- 01/01/2018
Facility
- Application
- Petrochemical industry
- Sub-application
- dewaxing unit
- Hydrogen supply chain stage
- All components affected
distillate dewaxing unit, catalytic bead
- Process temperature range [C]
- High temperature (100°C to 500°C)
- Location type
- Open
- Location
- industrial area
- Operational condition
- Description of the facility/unit/process/substances
DESCRIPTION OF THE PROCESS
Catalytic dewaxing is a particular hydrocracking process used to improve cold flow properties of middle distillates and lubricants by cracking normal paraffin. The pipe failure occurred at the exit of the one of the two catalyst bed reactors of the distillate dewaxing Unit, on the line bringing the gas to the heat exchanger.The unit was undergoing hot hydrogen regeneration of the catalyst at the time of the explosion. Catalyst regeneration is a procedure performed periodically, in which the normal liquid hydrocarbon feed stops and a hydrogen-rich gas mixture is fed through the catalyst bed. The process occurs at a temperature (800 F, 430 C), higher than the operative temperature (700 F, 370 C).
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 5
- Post-event summary
The vapour cloud found an ignition source and the ensuing flash fire spread up to 230 feet west of the tank farm. A shock wave from the resulting explosion expanded through the adjacent neighbourhood, causing varied degrees of blast damage to residential homes.
Lesson Learnt
- Lesson Learnt
The accident was due to pipe walls being thinned due to corrosion that went undetected for years (no inspection record were found). Regular and adequate inspection is hence key to prevent such event.
In-depth data
- Release type
- gas mixture
- Involved substances (% vol)
- H2 80%
CH4 9.5% - Released amount (kg)
- 43
- Release temperature [°C]
- 430
- Probable IGNITION SOURCE
- Explosion type
- Detonation
- Flame type
References
- Sources categories
- CSB
- Reference & weblink
CBS investigation summary
https://www.csb.gov/-csb-releases-analysis-showing-cause-of-rupture-and…
(accessed January 2025)Final Metallurgical Analysis report by Exponent, June 19, 2013, subcontracted by CSB,
https://www.csb.gov/silver-eagle-refinery-flash-fire-and-explosion-and-…
(accessed November 2020)Salt lake City news of January 27, 2010
https://www.cityweekly.net/utah/utahs-unstable-oil-refineries/Content?o…
(accessed january 2025)Statement by Investigations Supervisor Don Holmstrom and CSB Chairman John Bresland, 11.17.2009,
https://www.csb.gov/silver-eagle-refinery-flash-fire-and-explosion-and-…
(accessed November 2020)Also uptaken by H2TOOLS
https://h2tools.org/lessons/pipe-ruptures-during-hydrogen-regeneration-…
(accessed December 2025)