A diesel and gas leak (H2, H2S, CH4) occurred in a hydrodesulphurisation unit (2,200 t/d). The leak location was on one of the boiler valves of the stabilization column.
The released mixture (390 °C / 35 bar) ignited, and due to the heat developed also other valves started leaking.
The compressor was stopped and the column isolated. The fire was extinguished in 35 minutes.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
France
Date
Component involved
valve (generic)
Failure mode
rupture & ignition
Initiating cause
material degradation (thermal stress/cycling)
Root CAUSE analysis

The ARIA report (see references) mentions that the failed valves were of a special type without flange (?) and that were subject during operation to heavy thermal and mechanical fluctuations, and had already experienced various incidents in the past.

Root causes
Date entry in HIAD
01/01/2018

Facility

Application
Petrochemical industry
Sub-application
Hydrodesulphurisation process
Hydrogen supply chain stage
All components affected

valve of a boiler. tabilisation unit

Process temperature range [C]
High temperature (100°C to 500°C)
Process pressure range [MPa]
medium pressure (2 to 10 MPa)
Location type
Open
Location
industrial area
Operational condition
Pre-event occurrences

These boiler valves which failed in this event had already experienced various incidents in the past.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Emergency action

The fire was extinguished in 35 minutes

Lesson Learnt

Corrective Measures

The ARIA report (see references) mention as corrective actions (1) the replacement of the failed valve, with another type and (2) improved design to protect them from mechanical and thermal stresses.

In-depth data

Release type
Gas-liquid mixture
Involved substances (% vol)
H2,
diesel
Release temperature [°C]
390
Probable IGNITION SOURCE

References

Sources categories
ARIA
Reference & weblink

Event description in the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/11292/
(accessed October 2020)