Hose rupture during hydrogen transfer

Event

Event ID
1138
Quality
Description

The incident occurred while transferring gaseous hydrogen from a tube trailer to a customer stationary supply system. The transfer hose ruptured and released hydrogen which ignited explosively. The resulting fire was allowed to “burn off” the hydrogen remaining in the trailer.
The involved hose was part of system used to maintain a continuous supply to the customer. This is achieved by having one trailer kept connected as a supply source, while refilling the second trailer. By every new delivery of hydrogen, the newly refilled trailer is then connected to the customer system, before the trailer in service is isolated and disconnected.

In this incident, the refilled trailer had just been connected to the customer pressure reducing station and the second trailer was in the process of being disconnected for return and refilling. While disconnecting the in-service trailer, the driver heard an unusual sound from the direction of the full trailer which had just been connected. Before he was able to investigate the source of the sound, there was an explosive ignition followed by a fire. This sequence of an explosion followed by a fire was confirmed by onsite surveillance cameras.

The location of the release was the hose. There was no breach of any of the cylinders comprising the tube trailer, nor did the burst discs on any of the manifold tubes activated during the following fire. The hose was not equipped with excess flow devices, therefore the fire continued being fed by the hydrogen in the trailer, and the non-metallic components of the hose were burned. Since the whole hose was destroyed, a root cause for the incident could not be determined.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
North America
Country
United States
Date
Component involved
hose (trailer)
Failure mode
rupture & ignition
Initiating cause
material degradation (generic)
Root CAUSE analysis

The INITIATING CAUSE was the rupture of the flexible hose.
The ROOT CAUSE is unknown, the hose was destroyed during fire, and was impossible to determine the cause.

Root causes
Date entry in HIAD
25/10/2024

Facility

Application
Hydrogen transport and distribution
Sub-application
CGH2 tube trailer
Hydrogen supply chain stage
All components affected

Hose

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
medium to high pressure (10 to 50 MPa)
Location type
Open
Location
airport or airborne
Operational condition
Pre-event occurrences

the refilled trailer had just been connected to the customer pressure reducing station .

Description of the facility/unit/process/substances

The tradional steel tubes trailers of the company could achieve a max capacity of 350 kg of hydrogen. Their nominal pressure ranged between 180 an d200 bar.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
2
Currency
US$
Property loss (onsite)
311.000
Post-event summary

PHMSA report does not mention any injury. The online news speaks of 1 trailer operator with 2-degress burns and one Burger King customer with ear pain.
The total costs consisted of:
Material Loss: $ 1,000.00
Carrier Damage: $ 120,000.00
Property Damage: $ 150,000.00
Response Cost: $ 30,000.00
Remediation/Cleanup Cost: $ 10,000.00

Emergency action

The resulting fire was allowed to “burn off” the hydrogen remaining in the trailer.
The videos show intervention of fire brigades with water jets.
The airport was shutdown for approximately 1 hour, some flights were diverted mid-air, and the roadways in the area closed.

The DOT report specifies that the day after the hydrogen trailer company perofmrned a control release of the hydrogen stil in teh trailer, for a total of 25000 pounds. (approximately 1100 kg, much more than the value provided by PHMSA). It probably relates to th total capacity of two trailers. The measures was needed to be able to take away the damaged trailers.

Lesson Learnt

Lesson Learnt

An excess flow valve could be a possible measure to prevent large quantities of hydrogen to be lost when a leak occurs on a hose during hydrogen transfer. However, such a measure requires a careful design (the value of limit flow, the valve location, etc.), a complete review of the worst failure scenarios and of the related risk assessment, to avoid introducing additional hazards (for example when a quick venting is required to reduce over-pressurisation of the storage tank).

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Released amount (kg)
279.96253824
Release temperature [°C]
25
Release pressure [MPa]
18
Probable IGNITION SOURCE
Explosion type

References

Sources categories
PHMSA
Reference & weblink

Incident I-2011010130 of the US Pipeline and Hazardous Materials Safety Administration PHMSA:
https://portal.phmsa.dot.gov/analytics/saw.dll?Portalpages&PortalPath=%…
(accessed September 2024)

U.S. Department of Transportation,
Safety and Operations of Hydrogen Fuel Infrastructure in Northern Climates –– A Collaborative Complex Systems Approach
Final Project Report, Grant No. DTOS59-06-G-00048
https://rosap.ntl.bts.gov/view/dot/23734/dot_23734_DS1.pdf
(accessed July 2025)