Description

A gas leak containing hydrogen and hydrogen sulphide (H2S) occurred at the upper isolation valve located at a high-pressure separator (300 bar). This unit spearates the process gases from process liquids. The liquid is then sent to the low-pressure separator, while the gases leave via the upper isolation valve.

To control this valve, two measurements of the level of the mixture are necessary to prevent the entry of gas into the low-pressure section. A maintenance intervention was scheduled to replace one of the faulty level sensor. During the operation, the piece used to operate the valve broke without causing a leak. Thirty minutes later, the upper part of the valve was ejected under the effect of pressure, causing the release of about 25 litres of hydrogen.

The leak occurred 4 m aboveground and had no direct impact on staff. After depressurisation by gas flare, the equipment was purged by inert gas (nitrogen), which caused several successive sudden rises in pressure within the gas flare network along with the valve release. The amount of gas released by the gas flare during the day was estimated at 13 tonnes.

Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
leak no ignition
Macro-region
Europe
Country
France
Date
Component involved
valve (generic)
Failure mode
rupture, no ignition
Initiating cause
unknown
Root CAUSE analysis

INITIATING cause of he leak was the failure of a valve in the high-pressure part of a gas separator.
Root cause was a design defect of that type of valve.

Root causes
Date entry in HIAD
01/01/2020

Facility

Application
Petrochemical industry
Sub-application
Hydrocracking process
Hydrogen supply chain stage
All components affected

high-pressure separator (300 bar) of an oil production unit

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
medium to high pressure (10 to 50 MPa)
Location type
Open
Location
industrial area
Operational condition
Pre-event occurrences

The incident occurred after repairs

Description of the facility/unit/process/substances

DESCRIPTION of the HIGH-PRESSURE SEPARATOR PROCESS
After hydrocracking under high pressure and temperature, the oil viscosity is adjusted by means of reaction with a catalyst, hydrogen and a load of distillates. At the outlet, the high-pressure separator enables gases to be separated from liquids, with the latter channelled towards the low-pressure section by opening a valve. The uncondensed gases in the high-pressure separator are mainly composed of H2 and H2S.
The gases leave the high-pressure separator through the upper isolation valve.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Post-event summary

No inury, negligible equipment damage, 13 tons of gas released.

Official legal action

The Classified Facilities Inspectorate noted these facts and requested from the operator an analysis of the causes of the event, as well as the corrective actions taken or planned.

Emergency action

After depressurisation by gas flare, the equipment was purged with nitrogen, which caused several successive and sudden rises in pressure within the gas flare network along with the valve release.

Lesson Learnt

Corrective Measures

The operator found a defect with the valve flaps and decided to replace all identical valves on the site with valves of a different design.

In-depth data

Release type
gas mixture
Involved substances (% vol)
H2,
H2S
Released amount (kg)
13000
Release temperature [°C]
25
Release pressure [MPa]
30
Probable IGNITION SOURCE

References

Sources categories
ARIA
Reference & weblink

ARIA data base event no. 33332
https://www.aria.developpement-durable.gouv.fr/accident/33332_en/?lang=…
(accessed December 2025)