Freezing of a valve on a LH2 tanker

Event

Event ID
379
Quality
Description

A liquid hydrogen tanker was returning empty to the home terminal after delivery to a customer. At a stop, the drivers executed a visual inspection of the vehicle and noticed an accumulation of ice under the valve seat of the pressure control valve activating at 17 psig (pcv-1).
The liquid hydrogen tank was equipped with two pressure control (or relief) valves, one activating at 17 psig (pcv-1), and a second at 50 psig (pcv-2). The first one should be active only when liquid hydrogen is present in the tank. When the tanker contained only residual gaseous hydrogen, the 17 psig safety should be inactive.
In this case, it appeared that the ice build-up allowed the pcv-1 safety valve to remain active, in addition to the pcv-2. This would have caused the pressure relieving at 17 psig instead of 50 psig. The driver vented the tanker down to 2 psig which released 7,680 standard cubic feet of hydrogen to the atmosphere. Before resuming the journey, the drivers assured that the valve pcv-1 had completely thawed and returned to ambient temperature.
The valve and associated piping was inspected after returning to the home terminal. No defects were noted. Occasional ice accumulation is normal.

Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
leak no ignition
Macro-region
North America
Country
United States
Date
Component involved
PRD (valve)
Failure mode
premature activation & venting
Initiating cause
ice formation
Root CAUSE analysis

The INTIATING CAUSE was the formation of ice at pressure control valve, which made it remaining active against the procedure.
This event could be classified as near miss, because the safety measures were not compromised, which functioned as required. On the contrary, the fact that the low-pressure control valve was still active would have triggered an early venting, far away from the maximum allowed pressure in the vessel.
According to the transport company, ice accumulation is a ‘normal’ phenomenon.
There is nevertheless a lack of clarity on how the ice could impede the de-activation of the control valve, and consequently on the question if this can have additional negative impact on safeguards, such as the difficulty to operate other valves.

Root causes
Date entry in HIAD
16/11/2024

Facility

Application
Hydrogen transport and distribution
Sub-application
LH2 tanker
Hydrogen supply chain stage
All components affected

PRD

Process temperature range [C]
cryogenic temperature (below -50°C)
Process pressure range [MPa]
low to medium pressure (below 2 MPa)
Location type
Open
Location
highway or similar
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Currency
US$
Property loss (onsite)
16

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Probable IGNITION SOURCE

References

Sources categories
PHMSA
Reference & weblink

Report I-1992100776 of the US Pipeline and Hazardous Materials Safety Administration PHMSA: