Skip to main content
Clean Hydrogen Partnership

Fire at a waste liquid storage tank

Event

Event ID
734
Quality
Description

When waste alkali solution was taken out of dumper trucks into a waste liquid storage tank, a reaction occurred in the tank. As a result, the solution in the tank foamed over it, and reached an incinerator burning waste wood, when all the waste solution got in flames.
The cause of the incident was the waste alkali solution, which had a heavier specific gravity than water and sank and came into contact with aluminium powder that had accumulated at the bottom the tank. This resulted in generation of hydrogen gas, which was ignited by fire at the incinerator.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Asia
Country
Japan
Date
Component involved
chemical storage tank (waste)
Failure mode
fire (generic)
Initiating cause
accidental hydrogen formation
Root CAUSE analysis

The INITIATING CAUSE was the accidental generation of hydrogen gas, ignited by fire at the incinerator.
The ROOT CAUSE was identified by the original report in:
(1) Organization factor
(2) Design mistake
(3) Prior assessment insufficient.

Root causes
Date entry in HIAD
01/01/2020

Facility

Application
Chemical industry
Sub-application
Chemical waste storage and disposal
Hydrogen supply chain stage
All components affected

iquidstorage tank, alkaly tank

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Location type
Unknown
Location
industrial area
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Currency
Yen
Property loss (onsite)
21.730.000
Post-event summary

21.73 million yen worth of property damage

In-depth data

Release type
Gas-liquid mixture
Involved substances (% vol)
H2,
KOH solution,
Al
Release temperature [°C]
25
Probable IGNITION SOURCE

References

Sources categories
RISCAD
Reference & weblink

Orignal source lost. RISCAD is closed.