Event
- Event ID
- 616
- Quality
- Description
The cause of the incident was a fault in a 15 kV circuit breaker voltage transformer which led to a bus bar fault. A short circuit occurred in the bus bar system in a transformer building, causing a fire in adjacent switches. This was followed by the tripping out of the three refinery turbo-alternators, cutting off the National Grid supply, and loss of refinery electrical power, steam and air supplies for some 30 minutes.
During the power loss and shutdown of plant, a hydrogen leak developed on a valve, and a tube of a fin-fan condense bank failed. Total damage attributed to the incident has been estimated at between 500,000 and 700,000 Frs.
The fire fighters were busy for one and a half hours, they had to face ventilation problems and to ensure effective electrical isolation, before opening up electrical equipment casings.
- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- fire
- Macro-region
- Europe
- Country
- France
- Date
- Component involved
- H2 coolant system (pipe)
- Failure mode
- leak & ignition
- Initiating cause
- conventional component failure (electricity, power)
- Root CAUSE analysis
Leak and short circuit, power supply failure
- Root causes
- Date entry in HIAD
- 01/01/2020
Facility
- Application
- Power plant
- Sub-application
- unspecified power plant
- Hydrogen supply chain stage
- All components affected
transformer and circuit breaker, hydrogen valve
- Process temperature range [C]
- Above ambient temperature (50°C to 100°C)
- Location type
- Confined
- Location
- industrial area
- Operational condition
- Pre-event occurrences
The pre-event related to the hydrogen-event was a short circuit occurred in a busbar system of a transformer building.
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
- Currency
- Francs
- Property loss (onsite)
- 700.000
- Post-event summary
The tanker and adjacent buildings were set on fire and workshops severely damaged. Cars nearby were also set on fire.
Total damage attributed to the incident has been estimated between 500,000 and 700,000 Frs.- Emergency action
Black toxic smoke prevented immediate access to the transformer building despite the opening of doors and ventilation panels, and difficulty was found in extinguishing the fires in the switch cubicles.
The fire fighting was not fully successful in the transformer building for about 1 1/2 hours, the time being employed in dealing with the ventilation problems and to ensure that effective electrical isolation had been established before opening up electrical equipment casings.
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Release temperature [°C]
- 25
- Probable IGNITION SOURCE
References
- Sources categories
- ICHEME
- Reference & weblink
Event nr 11679 of the UK database ICHEME in PDF format
https://www.icheme.org/knowledge/safety-centre/resources/accident-data/
(accessed October 2020)