Event

Event ID
616
Quality
Description

The cause of the incident was a fault in a 15 kV circuit breaker voltage transformer which led to a bus bar fault. A short circuit occurred in the bus bar system in a transformer building, causing a fire in adjacent switches. This was followed by the tripping out of the three refinery turbo-alternators, cutting off the National Grid supply, and loss of refinery electrical power, steam and air supplies for some 30 minutes.

During the power loss and shutdown of plant, a hydrogen leak developed on a valve, and a tube of a fin-fan condense bank failed. Total damage attributed to the incident has been estimated at between 500,000 and 700,000 Frs.

The fire fighters were busy for one and a half hours, they had to face ventilation problems and to ensure effective electrical isolation, before opening up electrical equipment casings.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
France
Date
Component involved
H2 coolant system (pipe)
Failure mode
leak & ignition
Initiating cause
conventional component failure (electricity, power)
Root CAUSE analysis

Leak and short circuit, power supply failure

Root causes
Date entry in HIAD
01/01/2020

Facility

Application
Power plant
Sub-application
unspecified power plant
Hydrogen supply chain stage
All components affected

transformer and circuit breaker, hydrogen valve

Process temperature range [C]
Above ambient temperature (50°C to 100°C)
Location type
Confined
Location
industrial area
Operational condition
Pre-event occurrences

The pre-event related to the hydrogen-event was a short circuit occurred in a busbar system of a transformer building.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Currency
Francs
Property loss (onsite)
700.000
Post-event summary

The tanker and adjacent buildings were set on fire and workshops severely damaged. Cars nearby were also set on fire.
Total damage attributed to the incident has been estimated between 500,000 and 700,000 Frs.

Emergency action

Black toxic smoke prevented immediate access to the transformer building despite the opening of doors and ventilation panels, and difficulty was found in extinguishing the fires in the switch cubicles.
The fire fighting was not fully successful in the transformer building for about 1 1/2 hours, the time being employed in dealing with the ventilation problems and to ensure that effective electrical isolation had been established before opening up electrical equipment casings.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Probable IGNITION SOURCE

References

Sources categories
ICHEME
Reference & weblink

Event nr 11679 of the UK database ICHEME in PDF format
https://www.icheme.org/knowledge/safety-centre/resources/accident-data/
(accessed October 2020)