Skip to main content
Clean Hydrogen Partnership

Fire from ma hydrogen purification unit

Event

Event ID
591
Quality
Description

The incident affected a hydrogen gas purification unit of a chemical plant. A hydrogen release and ignition occurred at the joint between a pressure gauge attached to the inlet piping of an adsorption cylinder.
The pressure gauge attached had been removed for periodic inspection. It was calibrated and then reinstalled in its original position. However, the joint of the pressure gauge valve became loose, causing hydrogen gas to leak and ignite.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Asia
Country
Japan
Date
Component involved
gauge/instrument (connection)
Failure mode
leak & ignition
Initiating cause
loss of tightness (wrong operation)
Root CAUSE analysis

The INITIATING CAUSE was the loosening of a joint on a hydrogen pipe.
The KHK report attributes the ROOT CAUSE to a wrong re-installation, without specifying if this was mainly a human error or a shortcoming of the installation procedure.

Root causes
Date entry in HIAD
01/05/2025

Facility

Application
Chemical industry
Sub-application
hydrogen purification unit
Hydrogen supply chain stage
All components affected

connection, pressure gauge

Location type
Unknown
Location
unknown
Operational condition
Pre-event occurrences

The pressure gauge had been removed for maintenance and calibration, and re-installed.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
1
Post-event summary

minor injury

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Probable IGNITION SOURCE

References

Sources categories
KHK
Reference & weblink

High Pressure Gas Accident Cases Database of the KHK (High Pressure Gas Safety Association):
https://www.khk.or.jp/public_information/incident_investigation/hpg_inc…
(accessed May 2025)