Fire from a LH2 trailer

Event

Event ID
1126
Quality
Description

An empty LH2 trailer was travelling back to the base to load new LH2, when one of the truck tyre (the inner tire on the driver’s side rear axle) blew causing sparks and smoke. The driver pulled over to the side of the highway and tried to extinguish the starting fire by a fire extinguisher. Since was not able to extinguish completely the fire, he reported the incident to the emergency number. Due to the heat of he fire, the pressure rose inside the LH2 tank and the Pressure Safety Valve (PSV) activated releasing hydrogen gas into the atmosphere through the vent stack. The vented hydrogen ignited, developing fire at the vent stack. The first responders were able to extinguish the fire by using a helium fire abatement system. Meanwhile the pressure inside the trailer had decreased below the PSV activation value, however the PSV did not reseat. Therefore, the hydrogen continued to slowly escape out of the vent stack. 6 hours later, a company employee arrived to the site performed a controlled venting, to reduce the pressure to a safe level and to allow the PSV to reclose. The intervention was successful and the pressure reduced from approximately 170 psi (11.7 bar) to 3-5 psi (0.2 – 0.3 bar).

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
North America
Country
United States
Date
Component involved
PRD (valve)
Failure mode
rupture & ignition
Initiating cause
conventional component failure (fire-tyres)
Root CAUSE analysis

The INITIAL CAUSE was a conventional fire on a truck tyre, which increased the temperature and consequently the pressure of the LH2 tank. The pressure control system of the trailer functioned as expected. The fire fighting strategy was successful. Nevertheless, regular inspections, and maintenance and replacement procedures are in place for critical components of heavy duty vehicles. These measures should be able to prevent negative consequences to the rest of the system. This is even more important for hazardous material transports. Shortcoming in these procedures could be suggested as ROOT CAUSE.

Root causes
Date entry in HIAD
09/09/2024

Facility

Application
Hydrogen transport and distribution
Sub-application
LH2 tanker
Hydrogen supply chain stage
All components affected

burst disc, vent

Process temperature range [C]
cryogenic temperature (below -50°C)
Process pressure range [MPa]
low to medium pressure (below 2 MPa)
Location type
Open
Location
highway or similar
Operational condition
Pre-event occurrences

A conventional fire started on the truck, initiating the series of events.

Description of the facility/unit/process/substances

DESCRIPTION OF THE UNIT The nominal capacity of the trailer was 10500 gallons (2800 kg of LH2)

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Currency
US$
Property loss (onsite)
60.000
Post-event summary

The LH2 was almost empty. 80 kg were assessed as vented.

Emergency action

The driver called the alarm number because he was not able to extinguish the tyre fire. Meanwhile the LH2 tank over-pressurised, the pressure relief valve activated and the escaping hydrogen ignited. The first responders were able to extinguish the fire by using a "helium fire abatement system'. The source does not specify what this system consists of. It may implies the use of a non-freezing inert gas system. Anyhow, they avoided the risk of blocking the pressure relief valve due to water freezing. 6 hours later, a company employee arrived to the site performed a controlled venting, to reduce the pressure to a safe level and to allow the PSV to reclose. The intervention was successful and the pressure reduced from approximately 170 psi (11.7 bar) to 3-5 psi (0.2 – 0.3 bar). During the incident, the highway was closed in both direction. The trailer was moved off of the interstate 9 hours after the start of the incident, and the traffic resumed a couple of hours later.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Released amount (kg)
80.450416351249
Release pressure [MPa]
<1.0
Probable IGNITION SOURCE

References

Sources categories
PHMSA
Reference & weblink

Incident E-2013100402 of the US Pipeline and Hazardous Materials Safety Administration PHMSA: https://portal.phmsa.dot.gov/analytics/saw.dll?Portalpages&PortalPath=%2Fshared%2FPublic%20Website%20Pages%2F_portal%2FHazmat%20Incident%20Report%20Search (accessed September 2024)