Skip to main content
Clean Hydrogen Partnership

Fire on a LH2 cryostat

Event

Event ID
327
Quality
Description

This event occurred when dismantling the cryostat. While a hot air dryer was being used to free a coupling in a hydrogen cryostat, a flash fire occurred.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
North America
Country
United States
Date
-
Component involved
cryogenic vessel
Failure mode
internal explosion
Initiating cause
inadequate or no purge
Root CAUSE analysis

The INITIATING CAUSE the formation of an air-hydrogen explosive mixture in the cryostat.
The temperature at the centre of the cryostat was sufficiently low to liquefy air. The ignition of the hydrogen-air mixture was probably due to a spark from an open filament of the dryer.
The prescribed requirements for purging and bringing cryostat to room temperature was circumvented.

The ROOT CAUSE a human error.

Root causes
Date entry in HIAD
30/10/2025

Facility

Application
Non-road vehicles
Sub-application
Aerospace
Hydrogen supply chain stage
All components affected

cryostat

Process temperature range [C]
cryogenic temperature (below -50°C)
Location type
Unknown
Location
unknown
Operational condition
Pre-event occurrences

The cryostat was being heated up and emptied (probably at the end of an experiment)

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0

Lesson Learnt

Lesson Learnt

In this event, the existing procedure for bringing back the cryostat to room temperature and to dismantle it were not followed. The report does not explain why , but it is easy to assume that the operators wished to accelerate the work and forced a quicker warming up of the coupling by using an heating equipment which clearly was not fitted for the purpose, because not being explosion proof. This suggests a lack of basic knowledge of hydrogen safety principles, and possibly also a lack of supervision or of communication.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Probable IGNITION SOURCE

References

Sources categories
ORDIN
Reference & weblink

Mishap no 37 in
P. L. Ordin, Review of hydrogen accidents and incidents in NASA operations, 1974, NASA TM X-71565
https://ntrs.nasa.gov/citations/19740020344

Hankinson and Lowesmith, Qualitative Risk Assessment of Hydrogen Liquefaction, Storage and Transportation, FCH JU project IDEALHY, Deliverable 3.10 (2013)
confidential
(accessed October 2025)

Lowesmith et al., Safety issues of the liquefaction, storage and transportation of liquid hydrogen: An analysis of incidents and HAZIDS, Int. J. Hydrogen energy (2014) https://doi.org/10.1016/j.ijhydene.2014.08.002