A fire in the hydrotreatment oven of a refinery

Event

Event ID
103
Quality
Description

An explosion, followed by a fire, happened in an oven belonging to the hydro-treatment unit. Following a shutdown, the tube, containing only gaseous products and hydrogen, had been affected by instable flows. In presence of a flows lower than nominal, the tube temperature raised up to its mechanical resistance limit. Under internal pressure, it failed with a longitudinal crack of ca. 750 mm
The unit was shut down and the fire extinguished by itself.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
France
Date
Component involved
pipe (generic)
Failure mode
rupture & ignition
Initiating cause
over-heating (wrong operation)
Root CAUSE analysis

The INITIATING CAUSE was the failure of a tube of the oven due to overheating.

The destabilisation of the operative conditions was due to shortcoming in the capacity to control the operative parameters, also due to lack of effective diagnostics by means of measuring gauges.

Root causes
Date entry in HIAD
28/02/2009

Facility

Application
Petrochemical industry
Sub-application
Hydrodesulphurisation process
Hydrogen supply chain stage
All components affected

Hydrotreatment unit

Location type
Unknown
Location
industrial area
Operational condition
Pre-event occurrences

The oven used for hydrotreatment of complex oils had been shut down 3 hours before.

Description of the facility/unit/process/substances

It is probable that the oven affected by the explosion was a heat exchanger used to pre-heat hydrogen and other process gases before entering he hydro-treatment reactor.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Post-event summary

As a maintenance was planned in January 2006, the unit will not restart before this date.

Official legal action

The unit could not restart before the conclusions of investigation and the subsequent updating of safety measures.

Emergency action

The Internal Operation Plan was launched. The unit was secured by using extinguishing means, isolatiing it, depressurising it and placing it under nitrogen.
The integrity of all equipment surrounding the oven was checked.

Lesson Learnt

Corrective Measures

The plant operator:
1) verified the soundness of the range of allowed operative conditions,
2) ensured the correct functioning of the thermocouples measuring the temperature of the tubes,
3) improved the operative procedures, in particular those regulating the transitory phases.

In-depth data

Release type
gas
Involved substances (% vol)
H2 (mainly)
Probable IGNITION SOURCE
Explosion type

References

Sources categories
ARIA
Reference & weblink

Event no. 52706 of the French database ARIA (accessed December 2020)