Event
- Event ID
- 103
- Quality
- Description
An explosion, followed by a fire, happened in an oven belonging to the hydro-treatment unit. Following a shutdown, the tube, containing only gaseous products and hydrogen, had been affected by instable flows. In presence of a flows lower than nominal, the tube temperature raised up to its mechanical resistance limit. Under internal pressure, it failed with a longitudinal crack of ca. 750 mm
The unit was shut down and the fire extinguished by itself.- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Macro-region
- Europe
- Country
- France
- Date
- Component involved
- pipe (generic)
- Failure mode
- rupture & ignition
- Initiating cause
- over-heating (wrong operation)
- Root CAUSE analysis
The INITIATING CAUSE was the failure of a tube of the oven due to overheating.
The destabilisation of the operative conditions was due to shortcoming in the capacity to control the operative parameters, also due to lack of effective diagnostics by means of measuring gauges.
- Root causes
- Date entry in HIAD
- 28/02/2009
Facility
- Application
- Petrochemical industry
- Sub-application
- Hydrodesulphurisation process
- Hydrogen supply chain stage
- All components affected
Hydrotreatment unit
- Location type
- Unknown
- Location
- industrial area
- Operational condition
- Pre-event occurrences
The oven used for hydrotreatment of complex oils had been shut down 3 hours before.
- Description of the facility/unit/process/substances
It is probable that the oven affected by the explosion was a heat exchanger used to pre-heat hydrogen and other process gases before entering he hydro-treatment reactor.
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
- Post-event summary
As a maintenance was planned in January 2006, the unit will not restart before this date.
- Official legal action
The unit could not restart before the conclusions of investigation and the subsequent updating of safety measures.
- Emergency action
The Internal Operation Plan was launched. The unit was secured by using extinguishing means, isolatiing it, depressurising it and placing it under nitrogen.
The integrity of all equipment surrounding the oven was checked.
Lesson Learnt
- Corrective Measures
The plant operator:
1) verified the soundness of the range of allowed operative conditions,
2) ensured the correct functioning of the thermocouples measuring the temperature of the tubes,
3) improved the operative procedures, in particular those regulating the transitory phases.
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 (mainly)
- Probable IGNITION SOURCE
- Explosion type
References
- Sources categories
- ARIA
- Reference & weblink
Event no. 52706 of the French database ARIA (accessed December 2020)