Fire in a hydro-refiner

Event

Event ID
626
Quality
Description

A tube in a hydrorefiner heater ruptured resulting in an extensive fire inside and outside the furnace. The main fire in the furnace was extinguished within 15 minutes and the escaping gas / vapour release from the ruptured tubes allowed to burn under controlled conditions. There were no injuries to personnel but the furnace suffered damage estimated at £10,000 (1973).

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
United Kingdom
Date
Component involved
heat exchanger (pipe)
Failure mode
rupture & ignition
Initiating cause
over-heating
Root CAUSE analysis

The investigations revealed that during changes in operating conditions a cold circulation start-up valve was opened by mistake resulting in liquid feed/hydrogen starvation of the heater tubes for a period of 35 minutes and eventual rupture of the tube with massive release of hydrogen and hydrocarbon vapours.

Root causes
Date entry in HIAD
01/01/2020

Facility

Application
Petrochemical industry
Sub-application
Hydrodesulphurisation process
Hydrogen supply chain stage
All components affected

heater, hydrotreatement furnace

Process temperature range [C]
High temperature (100°C to 500°C)
Process pressure range [MPa]
medium to high pressure (10 to 50 MPa)
Location type
Unknown
Location
industrial area
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Currency
UK£
Property loss (onsite)
10.000
Post-event summary

No injuries to personnel.
The furnace suffered damage estimated at £10,000 (1973), including four distorted tubes and certain refractory damage. Some cabling, electrical and instrument fittings on the outside of the heater were also badly burnt.

Lesson Learnt

Corrective Measures

1. Keep the 4" cold circulation start up valve locked in the `shut' position when the unit is on-stream and attach a `Danger, Valve Not to be Opened' tag to the valve wheel.
2. Fit tube skin thermocouples with maximum temperature alarms to the furnace to give warning of overheating.

In-depth data

Release type
gas mixture
Involved substances (% vol)
H2, hydrocarbons
Probable IGNITION SOURCE

References

Sources categories
ICHEME
Reference & weblink

Event description extracted from the UK database ICHEME in PDF

https://www.icheme.org/knowledge/safety-centre/resources/accident-data/
(accessed October 2020)