- Description
The incident occurred at the hydrogen coolant circuit, when purging the hydrogen with carbon dioxide and air, aiming at finding a leak. The explosion caused great damage to the turbine-generator unit and was felt by that residents 10km was misunderstood for an earthquake.
Following a preliminary investigation, the power plant company explained that hydrogen was still present when air was injected, creating the condition for the formation of an explosive mixture.- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Macro-region
- Africa
- Country
- South Africa
- Date
- Component involved
- H2 coolant system (pipe)
- Failure mode
- internal explosion
- Initiating cause
- inadequate or no purge
- Root CAUSE analysis
The INITIATING cause of the explosion was probably an inadequate purge procedure performed by injection of CO2 into the the hydrogel coolant system, followed by opening it to air. In presence of rest of hydrogen, air created the condition for an explosion. According to one of the sources, the internal pressure developed by the explosion could have been in the 5 to 10 MPa range. This assessment is based on the diameter and the tensile load of the bolts which failed.
Sources suggested that the explosion occurred due to deviation from the prescribed procedure. If confirmed, the root cause could be related to a human error or errors during the communication of the instructions. However, at 5 years from the explosion, there is no publicly available report providing a root case, which therefore remains unknown.
- Root causes
- Date entry in HIAD
- 01/01/2024
Facility
- Application
- Power plant
- Sub-application
- coal-fired power plant
- Hydrogen supply chain stage
- All components affected
hydrogen cooling system, turbine, generator
- Process temperature range [C]
- ambient temperature (-50°C to +50°C)
- Location type
- Confined
- Location
- industrial area
- Operational condition
- Pre-event occurrences
The plant was a new coal-fired power station with a nominal powerof 4.8GW.
At the moment of the incident, only few units were already in function. The unit affected, of approximately 800 MW, was on a short-term outage.
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
- Currency
- RSA Rand
- Property loss (onsite)
- 1.500.000.000
- Property loss (offsite)
- 0
- Post-event summary
No injuries have been reported. Emergency services attended to seven workers requiring treatment for shock.
The turbine hall and surrounding structures were affected: doors and windows of multiple structures were damaged, the roof sheeting blew off leaving the entire turbine hall area of the affected unit, as well as sections of other two units exposed to the elements. The damage to the generator was extensive (though not quanitfied by the owner).
Various sources estiamted the the costs ranging between 1.5 bn and 2.5 bn of rands (rough estimations not based on real damage assessment).
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Release temperature [°C]
- 25
- Probable IGNITION SOURCE
- Explosion type
References
- Sources categories
- News
- Reference & weblink
TECHCENTRAL news of 9 August 2021
https://techcentral.co.za/photos-extensive-damage-at-medupi-after-massi…
(accessed Jan 2022)TECHCENTRAL news of 9 August 2021
https://techcentral.co.za/photos-extensive-damage-at-medupi-after-massi…
(accessed Jan 2022)The Chemical Engineering news
https://www.thechemicalengineer.com/news/explosion-at-south-african-pow….
(accessed May2026)Global Energy Monitor page dedicated to the plant:
https://www.gem.wiki/Medupi_power_station#cite_note-39
(accessed May 2026)