Fire at a generator of a power plant

Event

Event ID
284
Quality
Description

Hydrogen fire in the compressor-turbine chamber of a power plant. The hydrogen leaked from the generator terminal bushing into unventilated terminal segregated bulbar ducting (this is a duct used for power cables).
Ignition source not stated.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
United Kingdom
Date
Component involved
H2 coolant system (rotating seal)
Failure mode
leak & ignition
Initiating cause
unknown
Root CAUSE analysis

INITIATING CAUSE
Hydrogen leak from the power generator coolant system

ROOT CAUSE
The fact hat the leaked hydrogen could access the electrical cable duct seems to point at shortcoming in risk assessment, reflected in shortcomings in design. It could be, however, also be a wrong installation of the components.

Root causes
Date entry in HIAD
28/02/2009

Facility

Application
Power plant
Sub-application
unspecified power plant
Hydrogen supply chain stage
All components affected

hydreogen seal,
generator, auxiliary duct

Process temperature range [C]
Above ambient temperature (50°C to 100°C)
Location type
Unknown
Location
unknown
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Probable IGNITION SOURCE

References

Sources categories
HSE
Reference & weblink

Event description provided by HSE, original source confidential