Skip to main content
Clean Hydrogen Partnership

Fire at a generator of a power plant

Event

Event ID
278
Quality
Description

The explosion occurred in the condenser area of a steam turbine, two hours after the unit tripped due to a stator earth fault.
The stator earth fault had damaged two hydrogen cooler tubes, which allowed hydrogen to pass from the stator casing into the condenser via the condensate system.
The ignition source was thought to be either via a contact with the hot metal of the steam chests or due to an electrostatic spark.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
United Kingdom
Date
Component involved
H2 coolant system
Failure mode
internal explosion
Initiating cause
conventional component failure (electricity, power)
Root CAUSE analysis

The INITIATING cause the leak of damaged hydrogen pipes.
Nothing can be said on the root cause, but the fact that the stator earth fault was able to damage the hydrogen pipe may be attributed to a design failure and/or shortcoming in the risk assessment.

Root causes
Date entry in HIAD
28/02/2009

Facility

Application
Power plant
Sub-application
unspecified power plant
Hydrogen supply chain stage
All components affected

hydrogen pipe

Process temperature range [C]
Above ambient temperature (50°C to 100°C)
Location type
Confined
Location
unknown
Operational condition
Pre-event occurrences

A stator earth fault had occurred two hors before the incident and damaged the hydrogen coolant system.

Description of the facility/unit/process/substances

DESCRIPTION OF A "STEAM CHEST"
The steam chest serves as a distribution point for the high-pressure steam coming from the boiler.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Probable IGNITION SOURCE
Explosion type

References

Sources categories
HSE
Reference & weblink

Event description provided by HSE, original source confidential