Fire on a compressor of a desulphurisation unit

Event

Event ID
761
Quality
Description

In a hydrodesulphurisation unit of a refinery, an operator which was performing a control tour heard noises and clicks on the hydrogen compressor and stopped it.
The compressor was of a reciprocating compressor with 2 opposite cylinders and 1 stage, operating at 60 bar. When the compressor was stopped, the cylinder broke and released hydrogen-rich gas that ignited 15 to 20 seconds later.
The suction separator tank was equipped with 2 level alarms, one of which was coupled with the safety emergency stop. Their good functioning had been tested and should have excluded the massive arrival of liquid. No precursors could be found in the control room. Oil was found in the discharge manifold and a presence of greasy deposits on the outer face of the piston and on the bottom of the cylinder. In addition, the valves were heavily fouled and the suction filter partially clogged with deposits. Non-compliance with procedures was one of the components causing the accident.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
France
Date
Component involved
compressor / booster / pump
Failure mode
rupture & ignition
Initiating cause
unknown
Root CAUSE analysis

The INITIATING CAUSE was clogging of the internal piping due to deposits.
ROOT CAUSE was the lack of effective maintenance and inspection. Non-compliance with procedures was one of the components causing the accident.

Root causes
Date entry in HIAD
01/01/2020

Facility

Application
Petrochemical industry
Sub-application
Hydrodesulphurisation process
Hydrogen supply chain stage
All components affected

hydrogen compressor

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
medium pressure (2 to 10 MPa)
Location type
Semiconfined
Location
industrial area
Operational condition
Pre-event occurrences

an operator heard noises and clicks on the hydrogen compressor and stopped it.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Post-event summary

Oil was found in the discharge manifold and a presence of greasy deposits on the outer face of the piston and on the bottom of the cylinder. In addition, the valves were heavily fouled and the suction filter partially clogged with deposits.

Emergency action

The operator stopped the compressor.

The suction separator tank was equipped with 2 level alarms, one of which was coupled with emergency stop. However, this did not worked.

In-depth data

Release type
Gas-liquid mixture
Involved substances (% vol)
H2,
hydrocarbons
Release temperature [°C]
25
Release pressure [MPa]
6
Probable IGNITION SOURCE