Event
- Event ID
- 1087
- Quality
- Description
The fire developed on a hydrogen bus during filling, and was detected due to the development of smoke and a smell of burned materials.
The power cable of the fuel cells system had overheated.- Event Initiating system
- Classification of the physical effects
- No Hydrogen Release
- Nature of the consequences
- Macro-region
- Europe
- Country
- France
- Date
- Component involved
- FCEV bus
- Failure mode
- fire (generic)
- Initiating cause
- conventional component failure (electricity, power)
- Root CAUSE analysis
The INITIATING cause was the overheating of an electrical cable during refuelling.
Two possible causes were proposed:
(1) the cable had been wrongly installed or fixed, or
(2) the electrical system had caused too high current in the cable.- Root causes
- Date entry in HIAD
- 01/07/2024
Facility
- Application
- Road vehicles
- Sub-application
- FCEV-bus
- Hydrogen supply chain stage
- All components affected
power cable
- Process temperature range [C]
- ambient temperature (-50°C to +50°C)
- Location type
- Confined
- Location
- unknown
- Operational condition
- Pre-event occurrences
It happened during refuelling
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
- Post-event summary
Nobody was in the proximity of the bus.
20 days of operation were lost.
Lesson Learnt
- Corrective Measures
(a) To ship the affected component to the headquarter for inspection
(b) To replacement of the affected component with a new one.
(c) To perform an inspection of the system on all the other buses in function.
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Release temperature [°C]
- 25
- Probable IGNITION SOURCE
References
- Sources categories
- Investigation report
- Reference & weblink
Provided to JRC by the operator of the facility (confidential)