Event
- Event ID
- 1065
- Quality
- Description
A fire broke out on the insulating plastic elements of an alkaline electrolyser in a unit of a chemical plant. The shift saw the smoke from the control room.
The first action was to drain the potash into a tank provided for this purpose and to shut down the electrolyser. The on-call electrician interrupted the electricity.
The safety technician brought the fire under control in less than 10 minutes using CO2 extinguishers. After approximately six hours, the unit was restarted.- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- fire
- Macro-region
- Europe
- Country
- France
- Date
- Component involved
- electrolytic cell
- Failure mode
- rupture & ignition
- Initiating cause
- malfunctioning (electrolyser, cross-over)
- Root CAUSE analysis
The INITIATING CAUSE of the event was potash leak on the electrolyser block that induced an electric arc between the electric block and the bus bar. This ignition caused a rise in temperature followed by the outbreak of fire.
ROOT CAUSE unknown.- Root causes
- Unknown
- Date entry in HIAD
- 01/07/2024
Facility
- Application
- Hydrogen production
- Sub-application
- water electrolysis
- Hydrogen supply chain stage
- All components affected
Alkaline electrolyser
- Location type
- Unknown
- Location
- unknown
- Operational condition
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
- Property loss (onsite)
- 0
- Emergency action
The following steps were taken:
• The potash was drained into a tank provided for this purpose and to shut down the electrolyser.
• The on-call electrician interrupted the electricity.
• A no-go area is defined with ribbons and the metallic curtain are opened to provide natural ventilation.
• The technician controls the electrolyser using a thermal camera.
• The safety technician brought the fire under control in less than 10 minutes using CO2 extinguishers.
• After approximately six hours, the unit is restarted.
Lesson Learnt
- Corrective Measures
Following the event, the operator implemented the following actions:
• Increase the frequency of predictive and preventive maintenance: preventive visit to each electrolyser with cleaning or repair if necessary;
• Add to the return of experience the occurrence of this event;
• Increase operator awareness.
In-depth data
- Release type
- liquid
- Involved substances (% vol)
- KOH (solution)
- Probable IGNITION SOURCE
References
- Sources categories
- ARIA
- Reference & weblink
Event 59900 of the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/59900/