Event
- Event ID
- 1080
- Quality
- Description
This incident occurred when subcontractor two workers were widening air vents on the roof of a building hosting a tank containing hydrogen chloride solution. This intervention was necessary to to improve hydrogen venting from the tank storage area. The hydrogen gas was a by-product of the chlorine-making process.
The two workers were operating an angle grinder, producing sparks which ignited the flammable atmosphere which evidently containing hydrogen. An explosion followed, with one casualty and one injured worker.
The HSE, in charge of the investigation, concluded: "The company failed to take adequate steps to prevent the risk of an explosion occurring during the construction work that was taking place at the plant near to a source of hydrogen gas."- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Macro-region
- Europe
- Country
- United Kingdom
- Date
- Component involved
- chemical storage tank (HCl)
- Failure mode
- rupture & ignition
- Initiating cause
- inadequate or no purge
- Root CAUSE analysis
The incident inquiry by the Health and Safety Executive found that the water service company was to blame for management shortcoming in risk assessment, safety measures implementation, operative procedures, and management of external workers. The workers were unaware of the existence of hydrogen gas or the hazards involved, and that they did not see any health and safety or danger signs on the building.
- Root causes
- Date entry in HIAD
- 01/07/2024
Facility
- Application
- Other
- Sub-application
- waste management
- Hydrogen supply chain stage
- All components affected
vent, tank
- Process temperature range [C]
- ambient temperature (-50°C to +50°C)
- Location type
- Confined
- Location
- industrial area
- Operational condition
- Pre-event occurrences
The involved tanks were originally installed as an open-air facility, which was self-venting. However, the company decided to create a building around it, to avoid exposure to the elements.
Emergency & Consequences
- Number of fatalities
- 1
- Number of injured persons
- 1
Lesson Learnt
- Lesson Learnt
These were the findings of the forensic investigation:
(1) The explosion occurred because of a build-up of hydrogen in the ducting beneath the roof, likely ignited by the grinder.
(2) The plant should have been shut down.
(3) No permit had been given for the work being carried out.
(4) A specific risk assessment should have been carried out, but had not been done.
(5) The area should have been verified safe, for example by means of gas detectors.
(6) Safety and hazard warning signs would have helped, but none were present on the roof of the building, and that there were very poor communication channels.
(7) That tanks involved should not have been enclosed (they were originally installed as an open-air facility, which was self-venting. However, the company had decided to create a building around it. to avoid exposure to the elements).
(8) Gas detectors should have been provided.
(9) The workers should have been supervised by the plant operator.
In-depth data
- Release type
- gas mixture
- Involved substances (% vol)
- H2,
Cl2 - Release temperature [°C]
- 25
- Probable IGNITION SOURCE
- Explosion type
References
- Sources categories
- News
- Reference & weblink
Irish Times news of 6 Dec 2006
(accessed aug 2023)BBC news of 7 Dec 2006
https://www.irishexaminer.com/news/arid-30288410.html
(accessed aug 2023)PSI Database ENSAD
https://www.psi.ch/en/ta/ensad
(not online since 2024)Irish Examiner news of 6 Dec 2006
https://www.irishexaminer.com/news/arid-30288410.html
(accessed aug 203)