Event
- Event ID
- 138
- Quality
- Description
An explosion of hydrogen gas occurred on a test bench at a factory manufacturing rocket engins. The effect was perceived several kilometres away.
The explosion was caused by the release of 8 kg of H2 (equivalent to 100 m³ of gas) from a section of gas line a under maintenance. A 6-inch flange had been left open, in addition a remotely-controlled valve was opened accidentally. The explosion was followed by a jet flame fed by additional 16 kg of hydrogen gas (200 m³).
The protrective panels were blown off, and debris was scattered within a 100-meter radius of the bench. No injuries were reported, even among the six employees working within a 10- to 50-meter radius of the explosion.
- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Macro-region
- Europe
- Country
- France
- Date
- Component involved
- valve (generic)
- Failure mode
- erroneous release & ignition
- Initiating cause
- wrong operation
- Root CAUSE analysis
THE INTIATING CAUSE was an accidental release from a compressed hydrogen supply system under maintenance.
The fact that to achieve this, two independently operated valves were opened, suggests that the ROOT CAUSE was not only due to a human error, but to shortcoming in the operative procedures prescribing what to do before and during maintenance. In fact, the hydrogen supply system affected by the explosion had just been used to a purpose different from its main application. it was probably not in the status expected by the team performing maintenance.- Root causes
- Date entry in HIAD
- 10/01/2026
Facility
- Application
- Non-road vehicles
- Sub-application
- Aerospace
- Hydrogen supply chain stage
- All components affected
valves, test bench
- Process temperature range [C]
- ambient temperature (-50°C to +50°C)
- Process pressure range [MPa]
- medium to high pressure (10 to 50 MPa)
- Location type
- Semiconfined
- Location
- industrial area
- Operational condition
- Pre-event occurrences
During the day, the damaged test bench, mainly used for testing turbopumps and generators, had been used for one of its secondary functions: supplying gaseous hydrogen at 200 bar to another test bench. To this purpose, liquid hydrogen was first evaporated and then compressed to 800 bar.
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Release temperature [°C]
- 25
- Release pressure [MPa]
- 20
- Probable IGNITION SOURCE
- Explosion type
References
- Sources categories
- ARIA
- Reference & weblink
HIAD_138 - event no. 31335 of French ARIA database
https://www.aria.developpement-durable.gouv.fr/accident/31355/
(accessed December 2025)