Event
- Event ID
- 217
- Quality
- Description
Workers were performing demolition on a disused furnace. While removing a 10 inch valve from a pipe used to supply coke gas fuel to the furnace, a flammable mixture was unexpectedly released. The flammable material consisted of methane, hydrogen, carbon monoxide and solid coke.
The blast occurred when gas from the line came into contact with heaters which have open flames to keep nearby equipment from freezing.The workers were not aware that there might be flammable material still in the pipe.
The accident resulted in the death of two workers and 5 others were injured. The two workers that died were working on a platform about 20 feet above the ground and did not have means to escape the fire.- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Macro-region
- North America
- Country
- United States
- Date
- Component involved
- pipe (generic)
- Failure mode
- internal explosion
- Initiating cause
- inadequate or no purge
- Root CAUSE analysis
The INITIATING CAUSE of the fire was the release of flammable substances from the a line under maintenance.
The IGNITION SOURE was provided by nearby open flames.
Root CAUSE was the inadequacy of the management systems for the supervision, planning, and execution of maintenance work.
A contributing CAUSE was the absence of a program to identify and address hazards during decommissioning and demolition operations (The workers were not aware of the possible presence of flammable material still in the pipe, and an effective purge was clearly not performed).- Root causes
- Date entry in HIAD
- 28/02/2009
Facility
- Application
- Steel and metals industry
- Sub-application
- Steel metallurgy
- Hydrogen supply chain stage
- All components affected
furnace, heater
- Process temperature range [C]
- ambient temperature (-50°C to +50°C)
- Process pressure range [MPa]
- low to medium pressure (below 2 MPa)
- Location type
- Confined
- Location
- industrial area
- Operational condition
- Pre-event occurrences
Workers were performing demolition on a disused furnace. Heaters with open flame were used. While removing a 25 cm diameter valve from a pipe used to supply coke gas fuel to the furnace, flammable liquid was unexpectedly released and ignited.
Emergency & Consequences
- Number of fatalities
- 2
- Number of injured persons
- 5
- Emergency action
Responding to the accident were emergency crews (fire and ambulance) from the town of Burns Harbour and the Division's internal plant protection forces
Lesson Learnt
- Corrective Measures
The CSB issued the following recommendations to the plant operator:
1. Implement a work authorization program that requires higher levels of management review, approval, and oversight for jobs that present higher levels of risk, such as opening lines potentially containing flammable liquids where there is no low point drain.
2. Monitor the accumulation and flammability of COG condensate throughout the mill and address potentially hazardous changes
3. Survey the mill for dead legs and implement a program for resolving the hazards. Develop guidance for plant personnel on the risks of dead legs and their prevention. Include dead legs in plant winterization planning4. Provide drains at low points in piping to allow for the safe draining of potentially flammable material.
6. Establish procedures to ensure that insulation is replaced when removed for maintenance.
7 Conduct periodic audits of work authorization, line and equipment opening, dead leg management programs, and decommissioning and demolition activities and share findings with the workforce.
8. Revise the Material Safety Data Sheet (MSDS) for COG condensate to highlight the potential flammability hazard.
9. Ensure that management trains employees and informs contractors with regard to the potential presence of flammable liquids when working with or opening COG condensate piping and equipment.
In-depth data
- Release type
- gas mixture
- Involved substances (% vol)
- H2 11%,
CH4 48%,
CO 14%,
CO2 7% - Probable IGNITION SOURCE
- Explosion type
References
- Sources categories
- CSB
- Reference & weblink
CSB investigation, available (accessed 2July 2020) at https://www.csb.gov/bethlehem-steel-corporation-gas-condensate-fire/
Event in the European database eMARS
https://emars.jrc.ec.europa.eu/en/emars/accident/view/3a92b490-a63e-405…
(accessed May 2026)