Event

Event ID
217
Quality
Description

Workers were performing demolition on a disused furnace. While removing a 10 inch valve from a pipe used to supply coke gas fuel to the furnace, a flammable mixture was unexpectedly released. The flammable material consisted of methane, hydrogen, carbon monoxide and solid coke.
The blast occurred when gas from the line came into contact with heaters which have open flames to keep nearby equipment from freezing.

The workers were not aware that there might be flammable material still in the pipe.
The accident resulted in the death of two workers and 5 others were injured. The two workers that died were working on a platform about 20 feet above the ground and did not have means to escape the fire.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
North America
Country
United States
Date
Component involved
pipe (generic)
Failure mode
internal explosion
Initiating cause
inadequate or no purge
Root CAUSE analysis

The INITIATING CAUSE of the fire was the release of flammable substances from the a line under maintenance.
The IGNITION SOURE was provided by nearby open flames.
Root CAUSE was the inadequacy of the management systems for the supervision, planning, and execution of maintenance work.
A contributing CAUSE was the absence of a program to identify and address hazards during decommissioning and demolition operations (The workers were not aware of the possible presence of flammable material still in the pipe, and an effective purge was clearly not performed).

Root causes
Date entry in HIAD
28/02/2009

Facility

Application
Steel and metals industry
Sub-application
Steel metallurgy
Hydrogen supply chain stage
All components affected

furnace, heater

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
low to medium pressure (below 2 MPa)
Location type
Confined
Location
industrial area
Operational condition
Pre-event occurrences

Workers were performing demolition on a disused furnace. Heaters with open flame were used. While removing a 25 cm diameter valve from a pipe used to supply coke gas fuel to the furnace, flammable liquid was unexpectedly released and ignited.

Emergency & Consequences

Number of fatalities
2
Number of injured persons
5
Emergency action

Responding to the accident were emergency crews (fire and ambulance) from the town of Burns Harbour and the Division's internal plant protection forces

Lesson Learnt

Corrective Measures

The CSB issued the following recommendations to the plant operator:

1. Implement a work authorization program that requires higher levels of management review, approval, and oversight for jobs that present higher levels of risk, such as opening lines potentially containing flammable liquids where there is no low point drain.

2. Monitor the accumulation and flammability of COG condensate throughout the mill and address potentially hazardous changes
3. Survey the mill for dead legs and implement a program for resolving the hazards. Develop guidance for plant personnel on the risks of dead legs and their prevention. Include dead legs in plant winterization planning

4. Provide drains at low points in piping to allow for the safe draining of potentially flammable material.

6. Establish procedures to ensure that insulation is replaced when removed for maintenance.

7 Conduct periodic audits of work authorization, line and equipment opening, dead leg management programs, and decommissioning and demolition activities and share findings with the workforce.

8. Revise the Material Safety Data Sheet (MSDS) for COG condensate to highlight the potential flammability hazard.

9. Ensure that management trains employees and informs contractors with regard to the potential presence of flammable liquids when working with or opening COG condensate piping and equipment.

In-depth data

Release type
gas mixture
Involved substances (% vol)
H2 11%,
CH4 48%,
CO 14%,
CO2 7%
Probable IGNITION SOURCE
Explosion type

References

Sources categories
CSB
Reference & weblink

CSB investigation, available (accessed 2July 2020) at https://www.csb.gov/bethlehem-steel-corporation-gas-condensate-fire/

Event in the European database eMARS
https://emars.jrc.ec.europa.eu/en/emars/accident/view/3a92b490-a63e-405…
(accessed May 2026)