Explosion in a silicon crystal growing reactor

Event

Event ID
476
Quality
Description

The incident happened in an a reactor for silicon crystal growing of electronic-grade. An explosion was located in scrubber tank of the facility, due to an increase of hydrogen in the entrainment separator.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
North America
Country
United States
Date
Component involved
chemical storage tank
Failure mode
internal explosion
Initiating cause
wrong operation
Root CAUSE analysis

The increase in hydrogen concentration was triggered by the shutdown of the scrubber including the exhaust fan. Therefore the ROOT CAUSE could be tentatively attributed to an inadequate safety design, unable to guarantee continuous availability of critical components (in this case, the capacity to vent)

Root causes
Date entry in HIAD
28/01/2026

Facility

Application
Electrical, electronics and micro-electronics industry
Sub-application
single crystal growing
Hydrogen supply chain stage
All components affected

scrubber tanl

Location type
Confined
Location
unknown
Operational condition
Description of the facility/unit/process/substances

DESCRIPTION OF THE PROCESS
To produce epitaxial silicon, a silicon-containing gas, such as trichlorosilane (SiHCl3) is introduced into the reaction chamber along with a carrier gas, usually hydrogen as ultra-high-purity carrier gas and chemical reducing agent. The reaction process gases are then sent to a scrubber, to capture and neutralize hazardous, toxic, and corrosive gases produced during the epitaxial deposition process (mainly hydrochloric acid HCl, Silanes SiH₄, rest of chlorosilanes, silicon oxides (particulates rest of the dopant precursors, such as arsine AsH₃ and phosphine PH₃). These substances are separated from the gas stream by reactive chemical liquids, usually an acidic or basic aqueous solution, and collected in a scrubber tank, while hydrogen is sent to the venting system.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Currency
US$
Property loss (onsite)
5.000

In-depth data

Release type
gas mixture
Probable IGNITION SOURCE
Explosion type

References

Sources categories
Zalosh
Reference & weblink

Table II - Industrial Incidents of Appendix A of Zalosh and Short
COMPARATIVE ANALYSIS OF HYDROGEN FIRE AND EXPLOSION INCIDENTS
Quarterly Report No. 2 for Period December 1, 1977 - February 28, 1978
https://www.osti.gov/biblio/6566131
(accessed September 2020)