Explosion at a rubber factory, caused by accidental hydrolysis of chemicals.

Event

Event ID
781
Quality
Description

At a rubber factory, an explosion occurred inside a lubricant container filled with 18 tonnes of tri-(nonylphenyl) phosphate (TNPP or TNPA).
This tank was stirred and maintained at 45°C. However, the heating circuit routed to the container had broken down 7 days earlier.
With the polluted TNPP scheduled for disposal, the accident occurred during a sawing operation to remove the walkway interfering with the manhole opening.
The TNPP substance underwent hydrolysis in contact with water leaking via the broken coil; the resultant phosphoric acid corroding the steel on the container caused hydrogen to form. The relatively slow hydrolysis reaction was no doubt catalysed by metal particles (rust, etc.).

A technician was seriously injured due to a fall.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
France
Date
Component involved
chemical storage tank
Failure mode
internal explosion
Initiating cause
accidental hydrogen formation
Root CAUSE analysis

INITIATING cause: the release of TNPP substance which underwent hydrolysis in contact with water leaking via the broken coil with consequent formation of hydrogen. Ignition very probably was catalysed by metal particles (rust, etc.).

Root causes
Date entry in HIAD
01/01/2020

Facility

Application
Chemical industry
Sub-application
rubbers production
Hydrogen supply chain stage
All components affected

a lubricant container filled with tri-(nonylphenyl) phosphite (TNPP or TNPA)

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Location type
Confined
Location
industrial area
Operational condition
Pre-event occurrences

This tank was typically stirred and maintained at 45°C; however, the heating circuit routed to the container had broken down 7 days earlier.
The accident occurred during a sawing operation to remove the walkway interfering with the manhole opening. The sawing operation was aiming at disposing polluted TNPP.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
1
Post-event summary

A technician was seriously injured due to a fall.

Emergency evaluation

A heating belt (with Tmax < T° of TNPP degradation) replaced the coil, and a posted instruction reminded workers of the product's sensitivity to water.

In-depth data

Release type
Gas-liquid mixture
Involved substances (% vol)
H2,
H3PO4,
tri-(nonylphenyl) phosphate
Release temperature [°C]
20
Probable IGNITION SOURCE
Explosion type

References

Sources categories
ARIA
Reference & weblink

ARIA data base
event no. 16467