Skip to main content
Clean Hydrogen Partnership

Explosion in an metallic products plant

Event

Event ID
746
Quality
Description

Five barrels of aluminium dust were removed from an outdoor dust collector, sealed and stored in the plant, near electrical panels.
One of the barrels had been contaminated with water, which exothermically reacted with the aluminium dust to form hydrogen gas. The top of the barrel deformed and glowed red. Smoke was observed and an employee sounded a vocal alarm.
The lid blew off the barrel and the mushroom cloud of aluminium dust exploded in a fireball. Nearby combustible material ignited and the sprinkler system activated. The closest employee, sustained second-degree burns of the arm and neck and went to the emergency room for treatment. Due to the warning, there were no other serious injuries.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
North America
Country
United States
Date
Component involved
chemical storage tank
Failure mode
internal (flow) blockage
Initiating cause
accidental hydrogen formation
Root CAUSE analysis

The barrel of aluminium dust outdoor dust collector was contaminated with water and produced hydrogen. The ROOT CAUSE is related to the absence of preventing and mitigating measures, in a plant dealing with aluminium dust. The risk of metallic dust are well known and should be considered in the safety design od the operations.

Root causes
Date entry in HIAD
01/01/2020

Facility

Application
Steel and metals industry
Sub-application
Al metallurgy
Hydrogen supply chain stage
All components affected

aluminium powder, dust collector, barrels

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Location type
Unknown
Location
industrial area
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
1
Post-event summary

Smoke from the barrel was observed and an employee sounded a vocal alarm. Despite the following explosion, only the closest employee was injured, Thanks to the warning, there were no other serious injuries.

In-depth data

Release type
gas
Involved substances (% vol)
H2,
H2O,
Al
Release temperature [°C]
25
Probable IGNITION SOURCE
Explosion type

References

Sources categories
OHSA
Reference & weblink

Occupational Safety and Health Administration OHSA Inspection no. 119577575
https://www.osha.gov/pls/imis/establishment.inspection_detail?id=119577…
(accessed November 2020)