Skip to main content
Clean Hydrogen Partnership

Explosion from iron powder

Event

Event ID
315
Quality
Description

Am explosion occurred when adding iron powder to an EDTA solution at 60 C in a chemical reactor (EDTA = Ethylene-diamine-tetra-acetic acid ).
Hydrogen was produced by a chemical reaction and ignited by static energy, probably due to the fact that the iron powder was coming from non-conducting polypropylene container (IBC = Intermediate Bulk Container).
Two workers were injured.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
United Kingdom
Date
Component involved
reactor / oven / furnace / test chamber
Failure mode
internal explosion
Initiating cause
accidental hydrogen formation
Root CAUSE analysis

INITIATING CAUSE:
the addition of iron to the EDTA solution triggered an unwanted dissociation producing hydrogen.

ROOT CAUSE
This is a case where the hazards were known, but the risk assessment was not properly done.

Root causes
Date entry in HIAD
28/02/2009

Facility

Application
Chemical industry
Sub-application
Organic chemicals production
Hydrogen supply chain stage
All components affected

chemical reactor

Location type
Unknown
Location
industrial area
Operational condition
Description of the facility/unit/process/substances

DESCRIPTION OF THE PROCESS
Ethylene-diamine-tetra-acetic acid (EDTA) is a chelating agent which can bind metals.
EDTA is used to solubilize iron(III) in water. In the absence of EDTA or similar chelating agents, ferric ions form insoluble solids and are thus not bioavailable.
It is used for example in the paper industry, to bleach pulp, and in agriculture, to treat diseases.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
2
Post-event summary

2 persons injured, one of which hospitalised for less than one week.

Official legal action

The company was found breaching the Health and Safety at Work Act of 1974, specifically Section 2(1): "It shall be the duty of every employer to ensure, so far as is reasonably practicable, the health, safety and welfare at work of all his employees."
The hazards related to hydrogen, explosive dust and ignition had all been recognised earlier by Company, but an inadequate risk assessment had been performed.
Nevertheless, it was considered that mitigation outweighs reasons for Prosecution

Lesson Learnt

Lesson Learnt

This is a case where the hazards were known, but the risk assessment was not properly done.

Corrective Measures

(1) To reduce liquid temperature and therefore the evolution of hydrogen; to feed 25 kg bags via earthed, worm-feed/hopper unit.

(2) To use 2 reactors - one for making up warm starter solution and one for pre-mixing iron powder.

(3) to increase and modify nitrogen feed, from the sparge ring at reactor base, to directly to top of liquid.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Probable IGNITION SOURCE
Explosion type

References

Sources categories
HSE
Reference & weblink

Event description provided by HSE, original source confidential