Skip to main content
Clean Hydrogen Partnership

Explosion ina chlor-alkali electrolyser

Event

Event ID
641
Quality
Description

An internal explosion occurred when restating a chlor-alkali electrolyser.
A power outage caused a lack of power to the electrolytic cells and to the pump supplying the electrolyte to the cells.
In absence of electrolyte flow, a high-temperature gas space formed above the electrolytic cell.
Upon restarting the power supply to the cells, a delay occurred in the re-start of the electrolyte supply pump. Without electrolyte, the ion exchange membranes in the electrolytic cell dried out and shrunk, producing cracks in some of them. This allowed hydrogen gas to mix with the chlorine gas system and to form gas within the explosive range, ignited by a spark.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Asia
Country
Japan
Date
Component involved
electrolytic cell (diaphragm)
Failure mode
rupture, no ignition
Initiating cause
malfunctioning (electrolyser, cross-over)
Root CAUSE analysis

The INITIATING CAUSE was a loss of power which triggered a series of degradations in the electrolytic cells and eventually the cross-over of hydrogen into the chlorine space.
The power loss had been caused by maintenance to the electrical equipment.
The H2-Cl2 explosive mixture was ignited by sparks generated when an operator increased the electric current.
For unexplained reasons, no gas analysis had been performed before re-starting the normal electrolyser operation. It is unclear if this was a consequence of a human error or a lack of adequate safety instruction. In general, it could be concluded that the risk management of the plant was inadequate and unable to manage unplanned shutdowns.

Root causes
Date entry in HIAD
30/03/2026

Facility

Application
Hydrogen stationary storage
Sub-application
GH2 storage
Hydrogen supply chain stage
All components affected

cylinder, blow-off pipe

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Location type
Unknown
Location
populated area
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
1
Post-event summary

One of source reported "Ten nearby residents who suffered coughing from inhaling the chlorine gas were taken to hospital for treatment. ". This is not confirmed by another souce, which mentioned only 1 light injury.

In-depth data

Release type
gas mixture
Involved substances (% vol)
H2,
Cl2
Release temperature [°C]
25
Probable IGNITION SOURCE
Explosion type

References

Sources categories
KHK
Reference & weblink

High Pressure Gas Accident Cases Database of the KHK (High Pressure Gas Safety Association):
https://www.khk.or.jp/public_information/incident_investigation/hpg_inc…
(accessed May 2025)

The first entry in HIAD was coming from RISCAD, which is now closed.