Explosion in a hydrogenation reactor

Event

Event ID
916
Quality
Description

A explosion occurred in a chemical manufacturing plant for the pharmaceutical and cosmetics industries, classified as high level Seveso), and affected its hydrogenation reactor.
At end of the hydrogenation cycle, the catalyst needed to be reactivated by explosure to hydrogen at high temperature. After that, two buffer tanks belonging to the hydrogenation unit were opened for cleaning, when the explosion occurred.

The operator initiated the emergency plan, evacuated personnel and secured the area. Two operators were injured.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
France
Date
Component involved
reactor / oven / furnace / test chamber
Failure mode
rupture & ignition
Initiating cause
inadequate or no purge
Root CAUSE analysis

INITIATING CAUSE of the explosion was the presence of hydrogen when opening to air the buffer tanks.

According to the ARIA report, the explosion was probably be due to the presence of hydrogen in the reactor, because the nitrogen purging was not performed despite the procedures in place.
The flammable mixture created by the entrance of air at the opening of the tanks was then ignited by a hot spot formed by a catalyst deposit (ruthenium on coal), which probably had become pyrophoric after activation.

Contributing to the ROOT CAUSE was the failing to apply the procedure to purge the tank with nitrogen. This failure could be attributed to a human error, possibly triggered by lack of training or lack of clarity of the procedures.

ROOT CAUSE is unknown, because it is not known why the procedure was no followed.

Root causes
Date entry in HIAD
01/01/2018

Facility

Application
Chemical industry
Sub-application
pharmeceutical and cosmeticals manufacturer
Hydrogen supply chain stage
All components affected

hydrogenation reactor, buffer tank

Location type
Confined
Location
industrial area
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
2
Post-event summary

Two operators in the vicinity of the reactor at the time of the explosion were injured.
The system was not damaged.

Emergency action

Following the explosion, the operator initiated the emergency plan, evacuated personnel and secured the area.

Lesson Learnt

Lesson Learnt

An additional measure, not mentioned in the ARIA report, would come from answering the question on why the procedure was not followed, and what can be put in place to guarantee/monitor that they are followed in the future.

Corrective Measures

The operator introduced the following two improvements
1. Review and re-assessment of the operative procedures
2. new training of the workers.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Probable IGNITION SOURCE
Explosion type
Detonation

References

Sources categories
ARIA
Reference & weblink

Event 52794 of the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/52794/
(accessed September 2020)