Skip to main content
Clean Hydrogen Partnership

Explosion of hydrogen and sodium borohydride in a pharmaceutical plant

Event

Event ID
784
Quality
Description

The loss of control of a reaction caused a fire in a pharmaceutical plant caused a reaction runaway and the rupture of a 6 m³ reactor. A cloud containing sodium borohydride and hydrogen was released.
The production manager evacuated the installation. When the cloud reached electrical equipment, an explosion occurred. The cooling circuit was damaged. The thermal oil leaked and ignited. The fire spread to a large part of the plant.
Firefighters intervened. The water of extinction was confined in basins. Storage tanks that were not affected by the fire were emptied. During the accident, 30 t of oil burned. 50% of the installations were destroyed, representing a damage of 12 M €.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
Spain
Date
Component involved
reactor / oven / furnace / test chamber
Failure mode
rupture & ignition
Initiating cause
run-away reaction
Root CAUSE analysis

INITIATING cause was a reaction runaway cause explosion of the reactor.

The runaway of the reaction was due to a change in the reaction temperature. In order to increase reaction efficiency, the temperature had been lowered from 50 ° C to 20 ° C. The accident occurred during the first production under these conditions. No risk analysis of this operative change had been made beforehand. The standard procedures of the group to which the plant belongs did not take into account the risk of runaway exothermic reactions.

ROOT CAUSE was a modification of the process parameters, without performing a risk assessment.

Root causes
Date entry in HIAD
01/01/2020

Facility

Application
Chemical industry
Sub-application
Pharmaceutical production
Hydrogen supply chain stage
All components affected

unspcified chemical reactor

Location type
Unknown
Location
industrial area
Operational condition
Pre-event occurrences

Reaction temperature in the reactor containing NABH4 and H2 was lowered from 50C to 20C.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Post-event summary

During the accident, 30 t of oil burned. 50% of the installations were destroyed, representing an damage of 12 M €.

Emergency action

The production manager evacuated the installation.

The fire spread to a large part of the plant. Firefighters intervened. The water of extinction was confined in basins. Storage tanks that were not affected by the fire were emptied.

Lesson Learnt

Corrective Measures

After the accident, the operator modified the Management of Change procedures.
This event was at the origin of an evolution of the regulations to integrate this experience feedback.

In-depth data

Release type
gas mixture
Involved substances (% vol)
H2,
NaBH4
Probable IGNITION SOURCE
Explosion type

References

Sources categories
ARIA
Reference & weblink

ARIA data base
event no. 50441

Event of the European database eMARS
https://emars.jrc.ec.europa.eu/en/emars/accident/view/c6df8789-b814-856…
(accessed May 2026)