Skip to main content
Clean Hydrogen Partnership

Explosion in an hazardous waste treatment plant, possible caused by hydrogen

Event

Event ID
806
Quality
Description

In the acid treatment room of a Seveso low-threshold hazardous waste treatment centre, an explosion occurred on a 250 m³ concrete tank containing acid sludge being neutralized.
The explosion occurred when the employee left the room and cut off the lighting of the building.

The building was evacuated. The employee, severely burned, was transported to the hospital.
Firefighters intervened. The concentration close to tank ceiling was 80% of the LFL. The operator filled the tank with water. The next day, the concentration was less than 10% of the LFL.
The upper hatch of the tank was torn off. 30 m² of false ceiling were blown.
The presence of H2 was suspected to be at the origin of the event. The company has never controlled this room so no reference explosion-related survey was available.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
France
Date
Component involved
chemical storage tank (waste)
Failure mode
rupture & ignition
Initiating cause
accidental hydrogen formation
Root CAUSE analysis

The lack of measurements and survey could suggest a failure in guaranteeing safe operation of the facility.

Root causes
Date entry in HIAD
01/01/2020

Facility

Application
Other
Sub-application
Chemical waste storage and disposal
Hydrogen supply chain stage
All components affected

hazardous waste treatment centre, acid treatment room

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Location type
Confined
Location
industrial area
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
1
Post-event summary

The employee, severely burned, was transported to the hospital.

The upper hatch of the tank was torn off. 30 m² of false ceiling were blown.

Emergency action

The building was evacuated. Firefighters intervened.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Probable IGNITION SOURCE
Explosion type

References

Sources categories
ARIA
Reference & weblink

ARIA data base
event no. 51639