Event
- Event ID
- 682
- Quality
- Description
The event occurred in the stack filter house and was preceded by anomalously high radiation level readings from a monitor in the vent stack. When two plant employees entered the filter house to check the trouble, they were exposed to a radiation level of 6 mR/hr and left.
Another employee, outfitted with proper protective clothing entered the area a few hours later and observed water on the floor and a mis overhead. He refilled the off-gas loop seals with water.The explosion occurred four hours later. The off-gas loop seals had been blown because of a back pressure generated by a partially blocked filter in the vent stack. The filter was clogged by water that had bypassed an improperly installed demister. Hydrogen escaping from the blown loop seal accumulated in the filter house and was ignited when a relay activated to isolate the loop seals.
- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Macro-region
- North America
- Country
- United States
- Date
- Component involved
- off-gas system (safeguars seal)
- Failure mode
- internal explosion
- Initiating cause
- over-pressurisation
- Root CAUSE analysis
The INITIATING CAUSE was the failure of the safeguards (water) seals, due to the build up of pressure due to a clogged filter and cumulation od hydrogen.
The hydrogen released into the vent building, created a flammable mixture with air and ignited from a relay arc.
The ROOT CAUSE could be attributed to the lack of process parameter control and emergency procedure. Hydrogen detection does not seem having been in place as safety measure, and the fact that the water seals had failed does not seem having triggered any mitigating action.- Root causes
- Date entry in HIAD
- 28/01/2026
Facility
- Application
- Power plant
- Sub-application
- Nuclear power plant - BWR
- Hydrogen supply chain stage
- All components affected
demsiter, filter, off-gas house
- Location type
- Confined
- Location
- unknown
- Operational condition
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 2
- Currency
- US$
- Property loss (onsite)
- 0
- Emergency action
unknown
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Probable IGNITION SOURCE
- Explosion type
References
- Sources categories
- Zalosh
- Reference & weblink
Reported at page 8 of Zalosh and Short report:
COMPARATIVE ANALYSIS OF HYDROGEN FIRE AND EXPLOSION INCIDENTS
Quarterly Report No. 2 for Period December 1, 1977 - February 28, 1978
https://www.osti.gov/biblio/6566131
(accessed September 2020)